Set Tsp Parameters (Transparent Slave Parameters); Set Heating Curve Of Second Heating Circuit On Controller - Theben RAMSES 856 Installation And Operating Manual

Heating controller
Table of Contents

Advertisement

Set TSP parameters
(Transparent Slave Parameters)
The TSP parameters are set in the SETTINGS menu.
 Confirm TSP-PARAMETER with OK.
15 parameters can be set (see below).
Parameter 0 includes the 5 systems/applications.
 Use + or – keys or rotary control to enter the
value and confirm by pressing OK.
The value is transferred to the OT Box RAMSES top2 OT.
15 parameters are available from 0–14:
0 System selection (1, 2, 3, 4, 5 è default 1)
1 Boiler base temperature (10 ... 50 degrees, default 10 = off)
2 Max. feed temperature main circuit
(30 ... 90 degrees, default 80)
3 Max. feed temperature auxiliary circuit (rear mixer)
(30 ... 90 degrees, default 40)
4 Boiler hysteresis (1 ... 15 K, default 5)
5 Domestic hot water hysteresis (1 ... 10 K, default 5)
6 Domestic hot water priority / parallel operation (default ...)
7 Domestic hot water pump switch-off delay (0 ... 20 mins,
default 10)
8 Domestic hot water for frost protection (default ...)
9 Time for domestic hot water circulation pump:
0: Domestic hot water circulation pump only runs
when temperature-controlled
0–99: Domestic hot water circulation pump via ΔT on,
Value is the maximum runtime in s
10 Pump protection time (0 .. 11 pm, default 12)
11 Pump protection duration in s (0...99, default 15,
0 = no pump protection)
12 ΔT for sequence control (5 ... 25, default 15) resolution 0.1 K
13 ΔT1 for pump switch heater 1 (5 .. 15 K, default 5 K)
14 ΔT1 for pump switch heater 2 (5 .. 15 K, default 5 K)
Further information available in product
manual for OT box RAMSES top2 OT at
www.theben.de.

Set heating curve of second heating circuit on controller

The heating circuit is adjusted in the SETTINGS menu.
On the room thermostat RAMSES 850 top2 OT the heating curve for
2 heating circuits can be adjusted (see RAMSES 850 top2 OT oper-
ating guide, page 31). Base point2 and end point2, etc. must be set
on the room thermostat.
Setting range:
Base point 10–30 °C, default 20 °C
End point 25-60 °C, default 35 °C
8
TSP
PARAMETERS
TSP1
1
TSP2
10