Max - Initialization Based On Maximum Range - Samson 3730-5 Mounting And Operating Instructions

Electropneumatic positioner
Table of Contents

Advertisement

Closed position AIR TO CLOSE
If the slide switch is set to AIR TO CLOSE, the
positioner automatically switches to the di-
rection of action increasing/decreasing (äæ)
after initialization has been completed. This
results in the following assignment between
set point and valve position:
Direction of
Closed position
action
Actuator stem
extends (FA)

AIR TO OPEN
Actuator stem
retracts (FE)

AIR TO CLOSE
The tight-closing function has been activated.
Set Code 15 (final position w>) to 99 % for
three-way valves.
Canceling an initialization process
An initialization procedure in progress can
be canceled by pressing the rotary pushbut-
). STOP appears for three seconds on
ton (
the display and the positioner then changes
to the fail-safe position.
Exit the fail-safe position again over Code 0
(see section 8.2.2).
EB 8384-5 EN
Set point
Valve
CLOSED
OPEN at
at
0 %
100 %
100 %
0 %
7.6.1
MAX – Initialization
based on maximum
range
The positioner determines travel/angle of ro-
tation of the closing member from the
CLOSED position to the opposite travel stop
and adopts this travel/angle of rotation as
the operating range from 0 to 100 %.
Enable configuration:
Note:
If no settings are entered within 120
seconds, the enabled configuration
function becomes invalid.
g Code 3, display: No
Turn
, Code 3 blinks.
Press
Turn
 YES
Press
, display:
Select the initialization mode:
Turn
 Code 6
Press
.
Turn
 MAX
Start-up and settings
Default: No
Default MAX
67