Applicable Extension Pipe For Each Model - Mitsubishi Electric MFZ-KA-VA Technical Data Manual

Hide thumbs Also See for MFZ-KA-VA:
Table of Contents

Advertisement

7

APPLICABLE EXTENSION PIPE FOR EACH MODEL

SUZ-KA25VA SUZ-KA25VAH
SUZ-KA35VA SUZ-KA35VAH
MAX. REFRIGERANT PIPING LENGTH
Models
SUZ-KA25VA
SUZ-KA35VA
SUZ-KA25VAH
SUZ-KA35VAH
MAX. HEIGHT DIFFERENCE
Indoor
unit
w Max. Height
difference 12m
w Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Outdoor unit
Models
SUZ-KA25VA
SUZ-KA25VAH
SUZ-KA35VA
SUZ-KA35VAH
Refrigerant piping
Max. length : m
A
20
Refrigerant Piping
Max. length
precharged
5m
6m
900
0
0
0
0
1,050
Piping size O.D : mm
Gas
Liquid
6.35
9.52
A
Refrigerant piping length (one way)
7m
10m
8m
9m
0
150
90
120
0
90
120
150
Calculation : Xg=30g/mo(Refrigerant piping length(m) - 5)
44
Outdoor unit
11m
12m
13m
14m
180
270
210
240
180
210
240
270
15m
20m
300
450
300
450

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents