Installation Procedure; Indoor Unit Installation; Installing Drain Pipe - Fujitsu 9370083002 Installation Instruction Sheet

Cassette type (vrf system)
Table of Contents

Advertisement

Install the air conditioner as follows.

1. INDOOR UNIT INSTALLATION

(1) Make the holes for installing in the ceiling. (Fig. 4)
(2) Install the hanging bolts (M10), refer to the position in Fig. 3.
(3) Install special nut A, then special nut B onto the hanging bolt (Fig. 4).
(4) Raise the body and mount its hooks onto the hanging bolt between the special nuts.
(5) Turn special nut B to adjust the height of the body.
Fig. 3
(Grille measurement)
650 mm (25-15/32")
(Hanging bolt position)
400 mm (15-3/4")
1 Perform final tightening by tightening the double nut firmly. The product may fall if not installed properly.
2 Using a level, or vinyl hose filled with water, fine adjust so that the body is level.

2. INSTALLING DRAIN PIPE

Install the drain pipe in accordance with the instructions in this installation instruction sheet and keep the area
warm enough to prevent condensation. Problems with the piping may lead to water leaks.
Use general hard polyvinyl chloride pipe (VP25) [outside diam-
eter 32 mm (1-1/4")] and connect it with adhesive (polyvinyl chlo-
ride) so that there is no leakage.
Always heat insulate the indoor side of the drain pipe.
• Do not provide a rise, trap and air bleeding.
• Provide a downward gradient (1/50 to 1/100).
• Provide supports when long pipes are installed.
• When desiring a high drain pipe height, raise it up to 400 mm
(15") or less from the ceiling within a range of 150 mm (6") from
the body. A rise dimension over this range will cause leakage.

INSTALLATION PROCEDURE

Fig. 4
46 mm (1-27/32")
86 mm (3-3/8")
WARNING
CAUTION
Fig. 5
Supporter
40 mm (1-9/16")
Drain pipe
(Ceiling opening measurement)
( 600 mm ( 23-5/8"))
Special nut A
Special nut B
Hanging bolt
Hook
15 mm (19/32")
Rise
Trap
Gradient 1/50 to 1/100
150 mm (6") or less
1.5 to 2 m
(5 to 6.5 ft)
30 mm
or more
Ceiling
Air bleeding
Max. 400 mm
(15")
En-3