Code Fault
AF
Auxiliary fault
input shutdown
CO-1
Carbon monoxide
shutdown
CO-2
Carbon monoxide
shutdown
CO-3
Carbon monoxide
sensor shutdown
HE
High engine
temperature
shutdown
LOC
Loss of coolant
shutdown
LOP
Low oil pressure
shutdown
OC
Overcrank
shutdown
OF
Overfrequency
shutdown
OS
Overspeed
shutdown
OU
Overvoltage
shutdown
UF
Underfrequency
shutdown
UU
Undervoltage
shutdown
SCF0
Controller error
Figure 2-5 ADC 2100 Fault Shutdown Codes
TP-6390 1/06
Description
Input from a customer-supplied switch that closes
when the fault is active. Shutdown occurs
0.3 seconds after the fault is detected. This protection
becomes active 3-seconds after crank disconnect.
Sensor fault shutdown occurs because of the
presence of CO.
Shutdown occurs because of the presence of CO or
deteriorating emission-control components (such as
the catalyst).
Shutdown occurs if communication is lost between the
CO sensor and the ADC.
Shutdown occurs if the engine coolant temperature
exceeds the maximum temperature for more than
5 seconds. This protection becomes active after the
engine reaches the crank disconnect speed.
Note: The high engine temperature shutdown
functions only when the coolant level is in the
operating range.
Shutdown occurs 5 seconds after a loss of coolant
condition is detected. This protection becomes active
10 seconds after the engine has reached its stated
crank disconnect speed and remains active as long as
the generator run command is active.
Shutdown occurs if a low oil pressure condition exists
for more than 5 seconds. This protection becomes
active 30 seconds after the engine has reached crank
disconnect speed (30 second inhibit).
Note: The low oil pressure shutdown does not protect
against low oil level. Check the oil level at the engine.
Shutdown occurs after 3 unsuccessful starting
attempts. The crank cycle is set for three starting
attempts.
Shutdown occurs when the governed frequency
exceeds 110% of the system's frequency setpoint for
more than 5 seconds. This protection becomes active
10 seconds after engine start (10 second inhibit).
Shutdown occurs if the engine speed exceeds 115%
of the normal running speed for more than 0.3 seconds.
Shutdown occurs if the voltage exceeds 120% of the
voltage regulator setpoint for more than 2 seconds.
Shutdown occurs when the governed frequency falls
below 90% of the system's frequency setpoint for
more than 5 seconds. This protection becomes active
10 seconds after engine start (10-second inhibit).
Shutdown occurs if the voltage falls below 80% of the
voltage regulator setpoint for more than 10 seconds.
Indicates a software or communication problem within
the ADC 2100.
Check
Check the cause of the auxiliary fault.
Immediate service required. Contact an authorized
distributor/dealer for service.
Ensure windows are open for proper ventilation.
Operate the blower to expel dangerous fumes.
Move the vessel away from other vessels (as another
vessel may be the source for the presence of the CO).
Check the generator exhaust system (see Section 3.6).
Immediate service required. Contact an authorized
distributor/dealer for service.
Ensure windows are open for proper ventilation.
Operate the blower to expel dangerous fumes.
Move the vessel away from other vessels (as another
vessel may be the source for the presence of the CO).
Check the generator exhaust system (see Section 3.6).
Check the connections to the CO sensor.
If connections are okay, replace the CO sensor.
Contact an authorized distributor/dealer for service.
Check for a low engine coolant level.
Check for a clogged seawater intake or sea strainer.
Check for a damaged seawater pump impeller.
Check for leaks in the lubrication system.
Check the oil level and add oil if the level is low.
Check the fuel supply and battery.
If there is no output voltage, check the line circuit
breaker. Also check for loose connections.
Contact an authorized distributor/dealer for service if
problem continues.
Contact an authorized distributor/dealer for service if
problem continues.
Contact an authorized distributor/dealer for service if
problem continues.
Contact an authorized distributor/dealer for service if
problem continues.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for service if
problem continues.
Reduce the load and restart the generator set.
Contact an authorized distributor/dealer for service if
problem continues.
Contact an authorized distributor/dealer for service if
problem continues.