WEATHER PROOF AIR COOLED REMOTE
CONDENSER
The remote condenser versions of Cubers and
Flakers are similar to the air cooled standard
versions with the only difference of the remote
condenser and, on MC and MF series, of the Fan
Speed Control used to supply power to the fan
motor/s.

Technical specifications

1.
Remote air cooled condenser fit on proper
brackets
for
installation
(MV
installation only).
Cooling capacity with ΔT 15K is 4,5 KW
on MC 16/16 SHORT, MC 46, MF 56, MV
450 and MV 600; 6,0 KW on MV 800 and
MV 1000; 10,5 KW on MFE 61; 20,5 KW
on MF 83.
2.
Fan motor/s 220-240/50-60/1 - 135 Watts
- 0,6 Amps with IP 44 protection (against
liquids and solids) and flow rate of 2150
m³/hr (2 motors on MF 66; 3 motors on
MF 86).
3.
On MC and MF series only, an Electronic
Fan Speed Control set to 16 bar. On MV
series a standard ON-OFF hi pressure
control (15÷17 bars).
4.
Pre-charged refrigerant lines of 10 meters
length equipped with AEROQUIP quick
connections.
5.
Hi pressure safety control (manual reset
type) set to 34 bar on MC and MF series
(in place of the condenser temperature
sensor) and to 30 bar on MV series.
6.
Hi pressure control warning light.
rd
dd
horizontal
and
vertical
series
for
vertical
Remote Condenser
located ABOVE Ice
Machine
Remote Condenser
located BELOW Ice
Machine
Installation of the remote air cooled condenser
and pre-charged refrigerant lines
A.

Location considerations:

Select the best available place protected from
dirt/dust.
The weather proof remote air cooled condenser
can be installed indoor as well as outdoor and can
operate under the most different conditions (rain,
wing, snow, etc.)
Use the following formula for planning the location
of the condenser and ice machine.
Location Limits – Condenser location must
not exceed ANY of the following limits
Maximum vertical drop dd of 1 meter between the
icemaker and the remote condenser.
Maximum vertical rise rd of 3 meters.
Physical line set maximum length between
icemaker and remote condenser is 10 meters.
Limit to max. one rise and one drop.
Limit the calculated distance (CD) as per the
Calculation formula to 18 meters.
A = Drop = dd x 6.6
B = Rise = rd x 1.7
C = Horizontal run = hd x 1
CD = A + B + C
hd
Condenser Distance &
Location Schematic