Collective Installation And Continuous Installation - Mitsubishi Electric CITY MULTI PUHY-P-YMF-B Installation Manual

Outdoor unit
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
When unit is surrounded by walls
B
A
C
A L
or more
1
B L
or more
2
C Front
D Front panel
E Rear panel
Note:
Wall heights (H) of the front and the back sides shall be within
height of front panel and rear panel.
If the panel height is exceeded, add the "h" dimension of the
figure above to L
and L
in the table above.
1
2
Model
L
L
1
PUHY-P400
450
250
PUHY-P500
Example: When h is 100
The L
dimension becomes 450+100=550 mm.
1
When there is an obstruction above the unit
A
B
A 45° or more
B 300 mm or more
C Front
D 1000 mm or more
E Air outlet guide (Procured at the site)
F Rear
A
B
C
D
<Side view>
2
E
D
C
F
When there is little space
up to an obstruction
6.2. Collective installation and continu-
ous installation
Space required for collective installation and continuous installation:
When installing several units, leave the space between each block as
shown below considering passage for air and people.
E
A
C
B
C
*F
A
C
B
C
D
A
A (Must be open)
B Wall height (H)
C Front
D 1000 mm or more
E 250 mm or more
F 450 mm or more
G 900 mm or more
Note:
Open in the two directions.
In case wall height (H) exceeds overall height of unit, add "h"
dimension (h=wall height <H> – overall height of unit) to * marked
dimension.
If there is a wall at both the front and the rear of the unit, install
up to three units consecutively in the side direction and provide
a space of 1000 mm or more as inlet space/passage space for
each three units.
B
C
D
B
A
C
C
C
C
F
F
F
F
*E
A
B
C
D
B
C
D
*E
A
*F
B
E
G
A
E
E
A
G
7