APPLICATION
T841 Thermostats provide 24 Vac control of multistage
heating and cooling systems using manual changeover.
The T841D controls 1-stage heat and 2-stage cool and the
T841E controls 2-stage gas heat and 1-stage cool. The
T841D,E, provide HEAT-OFF-COOL system switching
and AUTO-ON fan switching.
Order Number
T841D
CHECK, HI SPD, LO SPD
T841E
HI, LOW
F R O N T O F D E V I C E
-S Y S T E M SWITCH
OPERATION
The T841E stages of heat make sequentially as the
temperature drops. Make refers to the mercury switch
initiating a call for heat or cool.
There is about 1 °F (0.6°C) between stages so the second
stage (auxiliary heat) makes only when the first stage
cannot handle the load. This 1°F is the interstage d
tial. The T841D stages of COOL-ON make sequentially as
the temperature rises.
®U.S. Registered Trademark
Copyright © 1997 Honeywell Inc.
Heating-Cooling Thermostats
Installation Instructions for the Trained Service Technician.
Table 1. Thermostat Features.
LEDs
Terminal Designations
R,G,W,B,L,X,Y1,Y2,O
R,G,W1,B,W2,Y
THERMOMETER
SETPOINT
SCALE
- LED (UP
TO THREE)
FAN SWITCH
Fig. 1. External view of T841.
i
fferen­
A ll Rights Reserved
INSTALLATION INSTRUCTIONS
Test holes are provided on the front of the thermostat to
accommodate test meter probes without removing the
thermostat from the wall. Remove the cover of the
thermostat to expose the test holes, which are labeled to
correspond with terminals on back of the thermostat. See
Fig. 1.
System Switch
HEAT-OFF-COOL
HEAT-OFF-COOL
COVER
MOUNTING
H OLES (4)
The light emitting diodes (LED) indicators light on certain
thermostats when something specific happens within the
system. Refer to the following list when the LED lights:
HI: Stage two of heat is operating.
LOW: Stage one of heat is operating.
CHECK: System needs to be checked. See heating
system instructions for specific meaning.
HI SPD: Stage two of cooling is operating.
LO SPD: Stage one of cooling is operating.
LEDs are not field replaceable.
Honeywell
T841D,E
Fan Switch
AUTO-ON
AUTO-ON
B A C K O F D E V I C E
W IRING TERM INAL 1
(UP TO 12)
Fig.
2
3
69-1066

Advertisement

loading

Summary of Contents for Honeywell t841e

  • Page 1 The T841D controls 1-stage heat and 2-stage cool and the thermostat from the wall. Remove the cover of the T841E controls 2-stage gas heat and 1-stage cool. The thermostat to expose the test holes, which are labeled to T841D,E, provide HEAT-OFF-COOL system switching correspond with terminals on back of the thermostat.
  • Page 2 T841D,E HEATING-COOLING THERMOSTATS This thermostat is a precision instrument and was carefully ® RECYCLING NOTICE adjusted at the factory. Handle carefully. This control contains mercury in a sealed tube. Do not place control in the trash at the end of its Mounting and Wiring useful life.
  • Page 3 T841D,E HEATING-COOLING THERMOSTATS Fig. 2. Internal schematic and typical wiring diagram fo r T841D. Provides 1-stage heating and 2-stage cooling control. Fig. 3. Internal schematic and typical w iring diagram fo r T841E. Provides 2-stage heating and 1-stage cooling control. 69-1066...
  • Page 4: Heat Anticipator Setting

    The heating anticipator is adjustable on the T841D and Move the system switch on the thermostat to HEAT and the first stage heating on the T841E. Move the adjustable the fan switch to AUTO. Move the setpoint lever to about indicator to match the current draw of the heating primary 10°F (6°C) above room temperature.

This manual is also suitable for:

T841d