Two Stage Gas Valve Adjustment; Gas Heat Operation; Proper Gas Flow - Lennox LGH 036 Installation Instructions Manual

Gas and cooling packaged units
Table of Contents

Advertisement

Two−Stage Gas Valve Adjustment
Gas manifold pressures should match pressures shown
in table 3. On two stage gas valves, initiate a W2
thermostat demand to check high fire pressure before low
fire pressure. With high fire operating, reduce the
thermostat demand to W1 and check the low fire
pressure. Refer to the Unit Controller manual to initiate a
thermostat demand.
IMPORTANT − Do not set low fire pressure lower than
the certified minimum input rating listed in table 3.
TABLE 3
MANIFOLD INPUT PRESSURES
Unit
Stage
+ 0.2
036, 048, 060, 072
Std./Med./High Heat
036, 048, 060, 072
Dual Heat
092− 360

Gas Heat Operation

See the operating instruction plate on the unit for details.
in.wg.
Propane (LP)
Natural Gas
Gas
1st
2nd
1st
Stage
Stage
+ 0.3
+ 0.2
NA
3.5
NA
1.7
3.5
5.1
1.6
3.7
5.5
Proper Gas Flow (Approximate)
1− Operate unit at least 15 minutes before checking gas
flow. Determine the time in seconds for two
revolutions of gas through the meter. (Two
revolutions assures a more accurate time.) A
portable LP gas meter (17Y44) is available for LP
applications.
2− Divide the number of seconds by two and
compare to the time in table 4. If manifold pressure is
correct and rate is incorrect, check gas orifices for
proper size and restriction.
3− Remove temporary gas meter if installed.
NOTE− To obtain accurate reading, shut off all other
gas appliances connected to meter.
GAS METER CLOCKING CHART
2nd
Stage
Unit
+ 0.3
Input
Rate
10.5
(Btuh)
10.5
65,000
78,000
10.5
105,000
125,000
130,000
150,000
169,000
180,000
240,000
260,000
360,000
480,000
Natural−1000 btu/cu ft
Note: Table assumes standard temperature (60°F), pressure
(30in.Hg.), and fuel heating values (Btuh/Ft.
corrections in altitudes above 2000 ft.
Page 5
TABLE 4
Seconds for One Revolution
Natural
1 cu ft
2 cu ft
1 cu ft
Dial
Dial
Dial
55
111
138
46
92
115
34
69
29
58
28
55
24
48
21
43
20
40
15
30
14
28
10
20
8
15
LP−2500 btu/cu ft
506373−01
LP
2 cu ft
Dial
277
231
86
171
72
144
69
138
60
120
53
107
50
100
38
75
35
69
30
50
19
38
3
). Apply pressure
11/2011