Bay–related parameters
6400 SETTINGS:
StatusBay 01–48?
6401 STATUS B 01 =active
6402 STATUS B 02 =active
.
.
.
6448 STATUS B 48 =active
6500 SETTINGS:
I>TripBay 01–48?
6501 I>TRIP BAY01 =.00
6502 I>TRIP BAY02 =.00
.
.
.
6548 I>TRIP BAY48 =.00
6600 SETTINGS:
BF OpMode 01–48?
6601 BF OPMD B01 =BZ unbalance
6602 BF OPMD B02 =BZ unbalance
.
.
.
6648 BF OPMD B48 =BZ unbalance
6700 SETTINGS:
I>BF
6701 I>BF BAY 01 =.50
6702 I>BF BAY 02 =.50
.
.
.
6748 I>BF BAY 48 =.50
_______________
I
– Nominal current of the bay current
N
transformer
(inactive, active)
(inactive, active)
(inactive, active)
1)
I/IN
(min.
1)
I/IN
(min.
1)
I/IN
(min.
(not existent, external,
BZ unbalance, trip rep/unbal, I>query,
trip rep/I>quer, trip rep/unb imp)
(like DA 6601)
(like DA 6601)
Bay 1–48?
1)
I/IN
(min.
1)
I/IN
(min.
1)
I/IN
(min.
0.00 – max.
25.00)
0.00 – max.
25.00)
0.00 – max.
25.00)
0.10 – max.
2.00)
0.10 – max.
2.00)
0.10 – max.
2.00)