Lennox HSXA12-018 Installation Instructions Manual page 17

Condensing outdoor units
Table of Contents

Advertisement

Approach Method and
Normal Operating Pressures
TXV Systems – Outdoor Temp. > 65_F (18_C)
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.
1 − Record outdoor ambient temperature using a digital
thermometer.
2 − Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3 − Compare stabilized pressures with those provided in
table 8, Normal Operating Pressures." Minor varia-
tions in these pressures may be expected due to differ-
ences in installations. Significant differences could
mean that the system is not properly charged or that a
problem exists with some component in the system.
Pressures higher than those listed indicate that the
system is overcharged. Pressures lower than those
listed indicate that the system is undercharged. Verify
adjusted charge using the approach method.
Approach Method
4 − Use the same digital thermometer you used to check
the outdoor ambient temperature to check the liquid
line temperature.
5 − The difference between the ambient and liquid temper-
atures should match values given in table 7. If the val-
ues don't agree with the those in table 7, add refriger-
ant to lower the approach temperature, or recover re-
Normal Operating Pressures In psig (liquid +/− 10 and vapor +/− 5 PSIG)*
Out. Coil
Entering Air
Mode
Mode
Temp
Temp.
°F (°C)
LIQ
65 (18.3)
238
75 (23.9)
275
fixed
85 (29.4)
317
orifice
ifi
95 (35.0)
362
105 (40.6)
410
65 (18.3)
234
75 (23.9)
270
TXV
85 (29.4)
312
95 (35.0)
361
105 (40.6)
409
*These are typical pressures only. Indoor indoor match up, indoor air quality, and indoor load will cause the pressures
to vary.
−018
−024
SUC
LIQ
SUC
LIQ
123
261
131
261
131
300
135
300
136
343
139
343
141
391
143
387
144
441
147
434
133
256
134
256
135
298
137
296
137
344
140
339
138
394
142
384
141
448
143
432
frigerant from the system to increase the approach
temperature.
Be aware of the R410A refrigerant cylinder. It will be
rose−colored. Refrigerant should be added through the
vapor valve in the liquid state. Some R410A cylinders
are equipped with a dip tube which allows you to
draw liquid refrigerant from the bottom of the cylin-
der without turning the cylinder upside−down. The
cylinder will be marked if it is equipped with a dip
tube.
HSXA12 Approach Values
Model No.
−018
−024
−030
−036
−042
−048
−060
Use table 8 to perform maintenance checks. Table 8
is not a procedure for charging the system. Minor
variations in these pressures may be due to differ-
ences in installations. Significant deviations could
mean that the system is not properly charged or that
a problem exists with some component in the system.
Table 8
−030
−036
SUC
LIQ
SUC
LIQ
128
268
130
254
133
308
134
296
138
351
138
340
141
398
142
389
145
447
146
440
137
264
135
256
139
305
138
296
141
349
139
341
144
396
140
389
146
446
143
440
Page 17
Table 7
Approach Temperature
Liquid Line −
Outdoor Ambient °F (°C)
10 (5.6)
12 (6.7)
13 (7.2)
12 (6.7)
11 (6.1)
13 (7.2)
14 (7.8)
IMPORTANT
−042
−048
SUC
LIQ
SUC
121
270
124
128
311
130
133
356
134
138
404
139
142
456
143
124
269
131
127
312
133
133
357
135
136
406
137
140
460
140
−060
LIQ
SUC
280
121
332
126
379
130
427
135
479
140
262
121
304
127
349
132
397
136
449
140

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents