Start−Up; Charging - Lennox HSXA12-018 Installation Instructions Manual

Condensing outdoor units
Table of Contents

Advertisement

3 − Connect the vacuum pump (with vacuum gauge) to the
center port of the manifold gauge set.
4 − Open both manifold valves and start the vacuum
pump.
5 − Evacuate the line set and indoor unit to an absolute
pressure of 23,000 microns (29.01 inches of mercu-
ry). During the early stages of evacuation, it is desir-
able to close the manifold gauge valve at least once to
determine if there is a rapid rise in absolute pressure.
A rapid rise in pressure indicates a relatively large leak.
If this occurs, repeat the leak testing procedure.
NOTE − The term absolute pressure means the total
actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.
6 − When the absolute pressure reaches 23,000 microns
(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit.
Close the manifold gauge valves.
WARNING
Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use com-
pressors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will
void warranty.
7 − Shut off the nitrogen cylinder and remove the manifold
gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.
8 − Reconnect the manifold gauge to the vacuum pump,
turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.
9 − When the absolute pressure requirement above has
been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set.
Start−Up
If unit is equipped with a crankcase heater, it should
be energized 24 hours before unit start−up to prevent
compressor damage as a result of slugging.
1 − Rotate fan to check for frozen bearings or binding.
2 − Inspect all factory− and field−installed wiring for loose
connections.
3 − After evacuation is complete, open the liquid line and
vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.
4 − Replace the stem caps and secure finger tight, then
tighten an additional one-sixth (1/6) of a turn.
5 − Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.
6 − Set the thermostat for a cooling demand. Turn on pow-
er to the indoor blower and close the outdoor unit dis-
connect switch to start the unit.
7 − Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.

Charging

This system is charged with R410A refrigerant which oper-
ates at much higher pressures than R22. The provided liq-
uid line filter drier is approved for use with R410A. Do not
replace it with components designed for use with R22. This
unit is NOT approved for use with coils which use capillary
tubes as a refrigerant metering device.
Units are factory charged with the amount of R410A refrig-
erant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with 15 ft.
(4.6 m) line set. For varying lengths of line set, refer to table
4 for refrigerant charge adjustment.
Liquid Line Set
Diameter
3/8 in.
(10 mm)
*If line length is greater than 15 ft. (4.6 m), add this amount. If line
length is less than 15 ft. (4.6 m), subtract this amount.
IMPORTANT
Mineral oils are not compatible with R410A. If oil
must be added, it must be a polyol ester oil.
Page 14
IMPORTANT
Factory Charge
Table 4
Oz. per 5 ft. (grams per 1.5 m) adjust
from 15 ft. (4.6 m) line set*
3 ounces per 5 feet
(85g per 1.5 m)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents