Adding refrigerant

18
E-
The outdoor unit is loaded with sufficient refrigerant for the standard
piping. Thus, refrigerant must be added if the piping is lengthened.
This operation can only be performed by a qualified refrigeration
specialist. For quantity of adding refrigerant, refer to page 19.
1
Check that the stop valve is closed entirely.
2
Charge the refrigerant through the service port of liquid stop valve.
N Do not charge the refrigerant through the gas side service port.
N N
o o
t t
e e
N N
o o
t t
e e
3
If you cannot charge the refrigerant according to the upper steps,
following these:
3-1 Open both liquid stop valve and gas stop valve.
3-2 Operate the air conditioner by pressing the K2 key on the outdoor
unit PCB.
3-3 About 30 minutes later, charge the refrigerant through the service
port of gas stop valve.
N If necessary, refer to the pressure table classified by outdoor
N N
N N
o o
o o
t t
t t
e e
e e
temperature.
Outdoor unit
Balance
Vacuum pump
Gas side stop valve(service port)
Liquid side stop valve(service port)