9.1.2 Determining the Length of a Common
Vent System
Follow the instructions listed below to determine the length of a
common vent.
1. Add the BTU/H input ratings for each unit in the cascading
system to determine the total BTU/H rating.
2. Determine the total length (L) of the common vent, which
consists of the horizontal width (W) and the vertical height (H):
Total length (L) = W + H.
H
W
Common Vent Length Table [Total Length (L) =
W + H]
Vent Length for NHB Boiler Units
Model
Required Load
(Total BTU/H)
NHB-110/150
300,000
2
450,000
3
600,000
4
750,000
5
900,000
6
1,050,000
7
1,200,000
8
Every 90° elbow used is equivalent to 8 linear feet (2.4
Note
m) of vent length.
Exhaust
D
Intake
Total Length (ft)
D=3"
D=4"
D=6"
D=8"
60
106
200
40
71
160
30
53
120
24
42
96
150
35
80
142
30
68
121
26
60
106
Example of a Typical Installation (Direct Vent Only)
The following illustration depicts an example of a common vent
system installed for a cascade system of 8 Navien NHB boiler units.
The illustration is intended for reference purposes
Note
only.
Installing a Common Vent System
61