▪ For the additional zone:
▪ The heat pump convectors are directly connected to the indoor
unit.
▪ The desired room temperature is set via the remote controller of
the heat pump convectors for each room.
▪ The heating demand signals of each heat pump convector are
connected in parallel to the digital input on the indoor unit
(X2M/1 and X2M/4). The indoor unit will only supply the desired
additional leaving water temperature when there is an actual
demand.
Configuration
Setting
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
In case of heat pump convectors:
External room thermostat for the
additional zone:
▪ #: [A.2.2.5]
▪ Code: [C-06]
Shut-off valve output
At the mixing valve station
Benefits
▪ Comfort.
▪ The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on the
actual room temperature (modulation).
▪ The combination of the two heat emitter systems provides the
excellent heating comfort of the under  floor heating, and the
rapid air heat up of the heat pump convectors (e.g., living
room=under  floor heating and the bedroom=convector (no
continuous heating)).
▪ Efficiency.
▪ Depending on the demand, the indoor unit supplies different
leaving water temperature matching the design temperature of
the different heat emitters.
▪ Under floor heating has the best performance with Altherma LT.
5.3
Setting up an auxiliary heat source
for space heating
▪ Space heating can be done by:
▪ The indoor unit
▪ An auxiliary boiler (field supply) connected to the system
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02
Value
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Note:
▪ Main room = user interface
used
as
room
thermostat
functionality
▪ Other rooms = external room
thermostat functionality
1 (2 LWT zones): Main +
additional
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition.
Set to follow the thermo demand
of the main zone.
Set the desired main leaving
water temperature.
5 Application guidelines
▪ When the room thermostat requests heating, the indoor unit or the
auxiliary boiler starts operating depending on the outdoor
temperature (status of the changeover to external heat source).
When the permission is given to the auxiliary boiler, the space
heating by the indoor unit is turned OFF.
▪ Bivalent operation is only possible for space heating, NOT for
domestic hot water production. Domestic hot water is always
produced by the DHW tank connected to the indoor unit.
INFORMATION
▪ During heating operation of the heat  pump, the
heat  pump
operates
temperature set via the user interface. When weather-
dependent operation is active, the water temperature is
determined automatically depending on the outdoor
temperature.
▪ During heating operation of the auxiliary boiler, the
auxiliary boiler operates to achieve the desired water
temperature set via the auxiliary boiler controller.
Setup
▪ Integrate the auxiliary boiler as follows:
e
a
c
d
b b
a
Indoor unit
b
Heat exchanger
c
Backup heater
d
Pump
e
Shut-off valve (field supply)
f
Non-return valve (field supply)
g
Shut-off valve (field supply)
h
Collector (field supply)
i
Auxiliary boiler (field supply)
j
Aquastat valve (field supply)
FHL1...3
Under floor heating
NOTICE
▪ Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
▪ Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.