Dc Power Supply Type - Mitsubishi FX3U-?*MR/ES User Manual

Fx3u series programmable controllers
Table of Contents

Advertisement

FX
Series Programmable Controllers
3U
User's Manual - Hardware Edition
9.3.2

DC Power Supply Type

Item
Supply voltage
Allowable supply voltage
range
Allowable instantaneous
power failure time
Power fuse
Power consumption
Rush current
24V DC service power
supply
5V DC built-in power
*2
supply
*1.
This power consumption is the value maximized by input/output extension blocks and special function
units/blocks connected to the main unit.
*2.
The power supply is not for external use.
The current capacity specified above is for the input/output extension blocks, special function blocks,
special adapters and expansion boards.
*3.
When supply voltage is 16.8 to 19.2V DC, the connectable extension equipment decreases.
For details, refer to Subsection 6.5.3 or 6.5.4.
176
FX
-16M /D
FX
3U
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
250V, 3.15A
*1
25W
→ For input/output powered extension units/blocks power consumption information,
9 Preparation for Wiring and Power Supply Wiring Procedures
Specifications
-32M /D
FX
-48M /D
3U
3U
24V DC
16.8 to 28.8V DC
30W
35W
35 A max. 0.5 ms or less/24V DC
500 mA or less
9.3 Power Supply Specifications
FX
-64M /D
FX
-80M /D
3U
3U
*3
250V, 5A
40W
refer to Section 15.2.
45W

Advertisement

Table of Contents
loading

Table of Contents