4.1.1 Serial Port J3

1
2
3
4
1
2
J3
3
4
Fig. 4.1.1-1 Serial port J3
The serial port J3 - RS232 is enabled
on all the units of the parallel system.

4.1.2 Output free potential contacts

The interface board provides 6 voltage free relay contacts giving some UPS critical alarms and
operation mode.
These signals are available either on connector J2- (sub D, female 25 pin) or terminal blocks X1.
The meaning of the alarms on the free contacts in standard configuration (default) is the following:
X1 / 1, 2, 3
X1 / 4, 5, 6
X1 / 7, 8, 9
X1 / 12, 13, 14
X1 / 15, 16, 17
X1 / 18, 19, 20
In case different alarms or operating status are required, they can be configured on the same terminals
via software from the control panel.
The configuration can be changed in Parameters Mode by a trained operator using the appropriate
password.
NOTE !
The programmable signals on X1 and J2 will be disabled with Q1 open, with the
exception of the signals for "16 - Manual Bypass ON" and "26 - EPO".
Modifications reserved
GE_UPS_OPM_SGS_ISG_10K_40K_0US_V070.docx
Serial port J3 - RS-232 (sub D, female 9 pin) that allows:
Total remote management of the system using software GE Power
Diagnostics, GE Data Protection or GE Service Software for system protection
and management of the UPS systems.
or
J2 / 1, 2, 3
or
J2 / 4, 5, 6
or
J2 / 7, 8, 9
J2 / 14, 15, 16
or
or
J2 / 17, 18, 19
J2 / 20, 21, 22
or
Critical Power
Fig. 4.1.1-2 Serial port J3 connection to PC with RS232 1:1 cable DB9m – DB9f
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
(NO, C, NC)
Utility Failure
Load on Inverter
Stop Operations
Load on Utility
General Alarm
Acoustic Alarm
Page 42/46
Installation Guide SG Series 10-20-30-40 UL S