Clearances - Bradford White VR-150-(kW) Installation And Service Manual

Commercial electric power water heater 12kw–162kw
Table of Contents

Advertisement

6. The floor on which the appliance is installed must be capable of supporting the total weight of the
water heater when completely filled with water. Combustible floor locations may be used. Maintain
required clearances from combustible surfaces.
7. The appliance must not be installed on carpet.
8. The appliance must be installed indoors where it is protected from exposure to wind, rain and
weather.
9. Locate the appliance as close as possible to the point of major hot water usage, the water piping
and branch electrical circuit wiring.
10. Insulate water piping to control heat loss and possible condensation.
11. The appliance must be located in an area that is not subject to freezing. The ambient temperature
of the space where the appliance is installed must not go below 32° F (0° C) or above 104° F (40°
C).
Installation of the water heater should be accomplished in such a manner that if the tank, piping or
any connections should leak, the flow of water will not cause damage to the structure. For this reason,
it is not advisable to install the water heater in an attic or upper floor. When such locations cannot be
avoided, a suitable drain pan must be installed under the water heater. Drain pans may be fabricated
or purchased from your plumbing wholesaler. The drain pan must be piped to an adequate drain.
Under no circumstances is the manufacturer to be held liable for any water damage in connection with
this water heater.
TABLE A – CLEARANCES FROM COMBUSTIBLE
CONSTRUCTION:
Right Side -
Rear
Left Side
Front
and heating elements
Top
Water Pipes
6" (15cm)
0"
Inspection Opening & Anode Rods
36" (0.91m) for service to controls
12" (30cm) for service access to
electrical service, water connections
and piping
1" (25.4mm)
CAUTION:
7