2.2 Jumper setup
2.2.1 JP0 ~ JP15 Analog Input R/C Filter
The OME-DB-889D provides R/C filter with each analog input channel by jumper
setting.
Channel 0 High
Channel 0 Low
Short : with filter
Default setting
2.2.2 JP16 Analog Output Channel Jumper
The OME-DB-889D supports 10 separate jumper to select output channel, This
feature permits up to 10 OME-DB-889D's be connected to a 10 channel analog input
card. Place the jumper in the output channel according to the channel of the analog
input card selected for that OME-DB-889D board. The following table illustrates the
jumper setting of using the OME-DB-889D with the OME-A-82X series.
JP16
X
Analog output
A/D CH0
A/D CH1
A/D CH2
A/D CH3
A/D CH4
A/D CH5
A/D CH6
A/D CH7
A/D CH8
A/D CH9
OME-DB-889D User's Manual
1.2KΩ
1.2KΩ
JP0~JP15
JP17
X
CJC output
0
1
2
3
4
5
6
7
8
9
1uF 50V
Open : Without filter
If none of the output channel is used,
leave the jumper in position "X". If
the CJC output is required for the
thermocouple applications, be aware
that the analog output and CJC output
share the connector for the analog
output and the CJC output.
Note: "X" means channels are not
supported by the OME-A-82Xseries
5