7
CORRECTION FACTORS
7-1. COOLING CAPACITY CORRECTION FACTORS
Outdoor unit
5m
PU(H)-P71VHA
1.00
PU(H)-P71YHA
PU(H)-P100VHA
1.00
PU(H)-P100YHA
PU(H)-P125YHA
1.00
PU(H)-P140YHA
1.00
7-2. HEATING CAPACITY CORRECTION FACTORS
Outdoor unit
5m
PUH-P71VHA
1.00
PUH-P71YHA
PUH-P100VHA
1.00
PUH-P100YHA
PUH-P125YHA
1.00
PUH-P140YHA
1.00
Refrigerant piping length (one way)
10m
30m
20m
0.988
0.966
0.946
0.985
0.957
0.931
0.981
0.946
0.914
0.976
0.931
0.893
Refrigerant piping length (one way)
10m
30m
20m
0.997
0.991
0.985
0.997
0.991
0.985
0.997
0.991
0.985
0.997
0.991
0.985
40m
50m
55m
0.929
0.913
0.905
0.908
0.886
0.876
0.885
0.858
0.845
0.858
0.827
0.813
40m
50m
55m
0.979
0.973
0.970
0.979
0.973
0.970
0.979
0.973
0.970
0.979
0.973
0.970
56