Boiler Location - Ferroli OPTIMAX 25 S Instructions For Use, Installation And Maintenance

Wall-mounting gas boiler, pre-mixed condensing system boiler
Table of Contents

Advertisement

Optimax 25 S

2.2 Boiler location

The unit's combustion circuit is sealed off from
the installation room. The installation room
must be suffi ciently well ventilated to prevent
any dangerous conditions from forming in the
event of even slight gas leakage. This safety
standard is required by the EEC Directive no.
90/396 for all gas units, including those with a
so-called sealed chamber.
Therefore the place of installation must be
free of dust, fl ammable materials or objects
or corrosive gases. The room must be dry and
not subject to freezing.
The boiler is designed to be installed on a solid
wall. The wall fi xing must ensure a stable and
effective support for the appliance, using the
bracket and fi xings supplied.
If the unit is enclosed in cupboard or moun-
ted alongside, there must be space for normal
maintenance work. Fig. 2 and tab. 1 give the
minimum clearances to leave around the unit.
A
fi g. 2
Table 1
Minimum
A
30 mm
B
200 mm
C
280 mm
15 mm
D
(via an openable panel)
A
Recommended
300 mm
300 mm
300 mm
> 600 mm
9