3. SERVICE AND MAINTENANCE

3.1 Adjustments

All adjustment and conversion operations must be carried out by Qualifi ed Personnel such as the per-
sonnel of the Local After-Sales Technical Service.
FERROLI declines any responsibility for damage or physical injury caused by unqualifi ed and unauthorized
persons tampering with the device.
Gas supply conversion
The unit can function with either Natural Gas or LPG and is factory-set for use with one of the two gases,
as clearly shown on the packing and on the unit's dataplate. Whenever a different gas to that for which
the unit is preset has to be used, a conversion kit will be required, proceeding as follows:
1 Remove the casing.
2 Open the airtight chamber.
3 Unscrew the gas coupling A on the air/gas mixer.
4 Replace the injector in the mixer with the one contained in the conversion kit.
5 Refi t the coupling A and check the connection is gastight.
6 Apply the sticker, contained in the conversion kit, near the dataplate.
7 Fit the airtight chamber and casing back on.
8 Check working pressure.
9 Set CO
mixture as detailed (page 26).
2
Nozzle Ø
fi g. 16
Natural gas
LPG
See Technical table
23