Starting; Stopping; Engine Care; Generator Care - North Star 8000 PPG Owner's Manual

Professional portable generator
Table of Contents

Advertisement

variation has no appreciable effect in the operation of
motors, lights and most
equipment and clocks will be affected if correct RPM is
not maintained. See Load vs. Output chart.
Load
Percent of
Speed
Generator
(RPM)
Output
0 %
3750
50 %
3600
100 %
3510
Output voltage should periodically be checked to
ensure continued proper operation of the generating
plant and appliances. Voltage can be checked with a
portable meter. Frequency can be checked using an
electric clock with a sweep second hand.
against a wristwatch or a stopwatch the clock should
be correct within +/- 2 seconds per minute. Speed
adjustments should be performed by a qualified
technician.
BEFORE STARTING
1. Make sure the generator is positioned on firm
level surface.
2. Check the crankcase for oil and maintain at a
proper level.
3. Check fuel level and fill tank 7/8 full with fresh
unleaded automotive gasoline.
completely to the top. Always wipe up and remove
any spilled gasoline.
4. Make sure that the exhaust fumes are directed
away from people.

STARTING

1. Disconnect all loads to generator.
2. Turn gas line valve to ON position.
3. Turn engine on-off switch located on engine to
ON position.
4. For cold engine, move choke lever to full choke
position, for warm engine, move choke lever to half
choke or to RUN position.
5. Grasp recoil handle and pull.
6. When engine starts, move choke lever to RUN
position.
7. Loads may now be connected to generator.

STOPPING

1. Disconnect all loads to generator.
2. Place engine on-off switch to OFF position.
3. Turn gas line valve to OFF position.
appliances.
Electronic
Output
Frequency
Generator
(Hz)
Voltage at 120V
Receptacle
62.5
129V
60.0
120V
58.5
112V
Timed
Never fill fuel tank

ENGINE CARE

Refer to your Honda Owner's Manual for proper
care and maintenance.
NOTE: When changing the oil on a hot engine, the
oil might overshoot the oil drain hole on the generator
base.

GENERATOR CARE

The generator head is a 2-pole, 3600 rpm, 60 Hz,
brushless, revolving field and synchronous type with
one sealed radial roller bearing.
generator head is directly connected to the engine
crankshaft and the stator is rigidly coupled to the
engine casting via the generator head casting.
Exercising the Generator - The generator
should be operated every four weeks. Warm the
unit by running the engine for 10 to 15 minutes. This
will dry out any moisture that has accumulated in the
windings. If left, this moisture can cause corrosion in
the winding. Frequent operation of the engine
generator will also ensure that the set is operating
properly should it be needed in an emergency.
Generator Maintenance - The generator head is
brushless and maintenance free.
service, including installation or replacement of parts
should be performed only by a qualified electrical
service
technician.
APPROVED REPAIR PARTS.
from Customer Service at 1-800-270-0810.
A. Bearing - The bearing used in these generators
is a heavy duty sealed roller bearing. They require no
maintenance or lubrication.
B. Receptacles - Quality receptacles have been
utilized. If a receptacle should become cracked or
otherwise damaged, replace it.
damaged receptacles can be both dangerous to the
operator and destructive to the equipment.
WARNING, Stand-by Operation
If your generator is to be used as a standby
electric power source in case of utility failure, it must
be installed by a registered and licensed electrician
and in compliance with all applicable state and local
electrical codes. Also, local Fire Departments must be
consulted concerning proper and safe handling
procedures for
generator to any existing electrical system without an
isolating, UL approved transfer switch, installed by a
licensed electrician.
8
The rotor of the
Major generator
USE
ONLY
Obtain factory parts
Using cracked or
gasoline.
NEVER
connect
FACTORY
any

Advertisement

Table of Contents
loading

This manual is also suitable for:

165914

Table of Contents