Main Functions
1.4
Fan Speed Control
Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and
For more information about Hall IC, refer to the troubleshooting for fan motor on page 81.
Phase Steps
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
LLL (Heating thermostat OFF)
LL (Cooling thermostat OFF)
SL (Silent)
L
ML
M
MH
H
HH (Powerful)
Note:
1. During powerful operation, fan operates H tap + 50 - 70 rpm.
2. Fan stops during defrost operation.
Automatic Air
The following drawing explains the principle for fan speed control for heating:
Flow Control for
Heating
Automatic Air
The following drawing explains the principle of fan speed control for cooling:
Flow Control for
Cooling
22
for Indoor Units
Step
= Within this range the airflow rate is automatically controlled when the FAN setting
button is set to automatic.
Thermostat
setting
temperature
0˚C
-1.5˚C
fan speed
fan speed
+2.5˚C
+1.5˚C
+0.5˚C
Thermostat
setting
temperature
Cooling
Heating
(R4085)
(R4085)
Phase control
L
-0.5˚C
ML
-2˚C
M
MH
+3˚C
M
+2˚C
ML
+1˚C
L
Phase control
hall IC
Dry mode
25/35kW class :
830 - 980 rpm
(During powerful operation :
1030 rpm)
Difference between room
and set temperature
(R3299)
Difference between room
and set temperature
(R3300)
Function and Control
Si04-604
control.