Unit Zone Addressing; Test System - Carrier Zone Manager Installation Manual

This control system only operates with indoor units.
Hide thumbs Also See for Zone Manager:
Table of Contents

Advertisement

Zone Manager
Unit zone addressing and control system

Unit zone addressing

The units must have their communications address changed to
the zone number in which they will occupy. Figure shows an
example using 9 units and 4 zones. For this example, the
values shown in Table 1 should be used. For this example,
units B, C, E, H, and I will occupy Zone 4. Therefore their
communications addresses should be configured to address 4.
The numbering of the zones must begin with Zone 1. Any
further zones must be added in a sequential order.
For example, configuring the zones 1, 2, 3, and 5 will result in
improper operation. (Fault code C4 would be seen).
Configuring the communications address using the
IR remote
The instructions below refer to the unit configuration shown in the
drawing.
• Each unit must have its own address ("UAdr" in the IR remote
control menu) which will be different from the others. The
example shows 9 units, so 9 different addresses will have to
be configured.
• Suppose you want to configure units A and D in room (zone)
1. Keeping the IR remote control OFF, press the keys mode
and louver
simultaneously for at least 5 seconds to
access to the 12 configuration menus.
Use "
" button to select item "UAdr" and then use
MODE
buttons to select address "1". Now press louver
send a message to unit "A". A "beep" confirms the address
reception.
Make sure one same address is not sent to the other units.
• Press
button to select address "2" and by means of louver
button send the message to unit "D".
Press mode
button again to select item "
and
buttons to select zone "1". Press louver
send the message to unit "A" and "D".
Configuration of unit "F" is made as follows:
• If "
" menu is still active, press
ZONE
"2". Press louver
button to send the message to unit "F".
A "beep" confirms message reception.
If more than 30 seconds have passed from configuration of unit
"D" , the IR remote control exits from the configuration menu
automatically.
If so, go back to the menu as previously described.
• By means of mode
button scroll all menus and select
item "UAdr". Use
button to select address "3". Press
louver
button to send the message to unit "F.
A "beep" confirms message reception.
UAdr=1/2
Unit A
ZONE=1
U=1
³
Unit D
U=2
U=4
U=3
Z=3
Z=2
·
»
Unit F
Unit G
Example unit configuration
Table 1: CCN addresses for units
Unit
A
B
Zone
1
4
Unit
1
5
address (UAdr)
button to
". Use
ZONE
button to
button to select zone
Unit C
Unit B
U=5
U=6
Z=4
¿
Unit E
U=8
U=9
Unit I
Unit H
C
D
E
F
G
H
4
1
4
2
3
4
6
2
7
3
4
9
and
Test System Installation
To assist with installation wiring and unit zone addressing
issues, an installation test mode exists, that allows the installer
to easily verify that all units, by zone, are communicating
properly with the Zone Manager.
• To enter installation test mode on the Zone Manager, depress
and hold the "
LOUVER
mode is entered, the display will show zone number and
"
F" in place of the system clock.
CON
• The only buttons that are active at this time are "
and "
END PROGRAM
The Zone Manager will continuously send out messages to the
units in the displayed zone, telling them to flash theirprotect
LED (RED) at a rate of 1 sec on and 1 sec off.
The installer can now visually verify that the units in the zone
are communicating properly with the Zone Manager.
The "
" button can be depressed to select a new zone
NEXT ZONE
to test. Once the zone is changed, all units in the new zone will
start blinking their protect LEDs, assuming addressing and
wiring is correct. The previous zone will time out and stop
U=7
blinking their protect LEDs (RED), after 10 seconds of not
receiving a message from the Zone Manager.
The installer should run this test on all zones in the system, verifying
that every unit is addressed and wired properly. When complete, the
installer can depress the "
Test Mode and have the Zone Manager operate normal again.
Once complete, the installer can be confident that the Zone
Manager will control all of the zones, based upon each zones'o
programming information.
I
4
8
E N G L I S H
A
A
1
F
B
2
AM
PM
Remote control
" button down for 5 seconds. When test
".
" button to disable Installation
END PROGRAM
"
NEXT ZONE
GB - 13