Fixing the Ourdoor Unit in Place
'X' mm
Rubber leg
Model
X
**
**
09/12/13
454
**
1
8/19
**
538
**
18/24
**
5
43
**
25
**
660

Final Check and Trial Operation

To complete the installation, perform the following checks and tests to
ensure that the air conditioner operates correctly.
Check the followings:
• Strength of the installation site
• Tightness of pipe connection to detect gas leak
• Electric wiring connection
• Heat-resistant insulation of the pipe
• Drainage
• Grounding conductor connection
• Correct operation (follow the steps below)
1. Press the Power
button and check the following:
The indicator on the indoor unit lights up.
2. Press the Mode button to select Cool or Heat mode.
In Cool mode, use Temp + or - button and set the temperature at 16°C.
In Heat mode, use Temp + or - button and set the temperature at 30°C.
• Approximately 3~5 minutes later, outdoor unit will start to operate and the Cool or Warm air will blow out.
• After 12 minutes of stationary condition check the indoor unit air treatment:
Cooling mode (indoor unit check) - Inlet air temp. - Outlet air temp : From 10°C to 12°C ( indicative delta T)
Heating mode (indoor unit check) - Outlet air temp. - Inlet air temp : From 11°C to 14°C (indicative delta T)
3. Press the Air swing
button and check the following:
4. Press the Power
button to stop the operation.
• When you complete the installation successfully, hand over this manual to the user for storage in a handy and safe
place.
Install the outdoor unit to a stable base to avoid the generation of noise and
vibration, especially when installing the unit close to a neighbor.
If you install the outdoor unit in a place exposed to strong winds or at a height,
to an appropriate support (wall or ground).
1
Place the outdoor unit as indicated on the top of the unit to let the
discharged air out properly.
2
Fix the outdoor unit to an appropriate support using anchor bolts.
Y
254
290
3
If the outdoor unit is exposed to strong winds, install shield plates around the
3
19
outdoor unit so that the fan can operate correctly.
340
S
ecure the rubber leg to prevent the generation of noise and vibration.
Outdoor size is di erent for model series. Please select correct outdoor
plate size.
37