Motor Rotates In The Opposite Direction; Speed Greatly Differs From The Setting; Acceleration/Deceleration Is Not Smooth - Mitsubishi Electric FR-E700 Instruction Manual

Fr-e740-016 to 300 - ec; fr-e720s-008 to 110 - ec
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Check first when you have some troubles
5.5.5

Motor rotates in the opposite direction

Check
points
Main
Phase sequence of output terminals U, V and W is
Circuit
incorrect.
The start signals (forward rotation, reverse rotation) are
connected improperly.
Input
Adjustment by the output frequency is improper during
signal
the reversible operation with Pr. 73 Analog input selection
setting.
Parameter
Pr. 40 RUN key rotation direction selection setting is
incorrect.
Setting
5.5.6

Speed greatly differs from the setting

Check
points
Frequency setting signal is incorrectly input.
Input
The input signal lines are affected by external EMI.
signal
Pr. 1, Pr. 2, Pr. 18, calibration parameter C2 to C7 settings
Parameter
are improper.
Setting
Pr. 31 to Pr. 36 (frequency jump) settings are improper.
Load
Parameter
Stall prevention is activated due to a heavy load.
Setting
Motor
5.5.7

Acceleration/deceleration is not smooth

Check
points
Acceleration/deceleration time is too short.
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F
control, so the stall prevention function is activated.
The base frequency does not match the motor
characteristics.
Parameter
Setting
Stall prevention function is activated due to a heavy
load.
Regeneration avoidance operation is performed
282
Possible Cause
Possible Cause
Possible Cause
Countermeasures
Connect phase sequence of the output cables (terminal
U, V, W) to the motor correctly
Check the wiring. (STF: forward rotation , STR: reverse
rotation)
Check the setting of Pr. 125, Pr. 126, C2 to C7.
Check the Pr. 40 setting.
Countermeasures
Measure the input signal level.
Take countermeasures against EMI such as using
shielded wires for input signal lines.
Check the settings of Pr. 1 Maximum frequency, Pr. 2
Minimum frequency, Pr. 18 High speed maximum frequency.
Check the calibration parameter C2 to C7 settings.
Narrow down the range of frequency jump.
Reduce the load weight.
Set Pr. 22 Stall prevention operation level higher according
to the load. (Setting Pr. 22 too large may result in
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.
Countermeasures
Increase acceleration/deceleration time.
Increase/decrease Pr. 0 Torque boost setting value by
0.5% increments to the setting.
For V/F control, set Pr. 3 Base frequency and Pr. 47 Second
V/F (base frequency).
For Advanced magnetic flux vector control or General-
purpose magnetic flux vector control, set Pr. 84 Rated
motor frequency.
Reduce the load weight.
Set Pr. 22 Stall prevention operation level higher according
to the load. (Setting Pr. 22 too large may result in
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.
If the frequency becomes unstable during regeneration
avoidance operation, decrease the setting of Pr. 886
Regeneration avoidance voltage gain.
Refer
to
page
16
20
170
257
Refer
to
page
38
88
170
89
84
Refer
to
page
101
77
90
112
84
246