Output Current Detection Function (Y12 Signal, Y13 Signal, Pr. 150 To Pr. 153) - Mitsubishi Electric FR-E700 Instruction Manual

Fr-e740-016 to 300 - ec; fr-e720s-008 to 110 - ec
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

4.11.7 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153)

The output current during inverter running can be detected and output to the output terminal.
Parameter
Name
Number
Output current detection
150
level
Output current detection
151
signal delay time
Zero current detection
152
level
Zero current detection
153
time
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 179)
Pr. 150
Pr. 151
Output current
OFF
detection signal
(Y12)
Pr. 152
Pr. 152
0[A]
OFF ON
Start signal
Zero current
OFF
detection time
(Y13)
* The zero current detection signal (Y13) holds the
signal for approximately 100ms once turned ON.
REMARKS
This function is also valid during execution of the offline auto tuning.
The response time of Y12 and Y13 signals is approximately 0.1s. Note that the response time changes according to the load
condition.
When Pr. 152 = "0", detection is disabled.
NOTE
Changing the terminal assignment using Pr. 190 to Pr. 192 (output terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
Function assignment of external terminal and control
Initial Value
150%
0s
5%
0.5s
Time
100ms
OFF
ON
100ms*
Time
OFF
ON
ON
Pr. 153
Pr. 153
Detection time
Detection time
Setting
Range
0 to 200%
100% is the rated inverter current.
Output current detection period.
The time from when the output current has risen
0 to 10s
above the setting until the output current detection
signal (Y12) is output.
0 to 200%
The rated inverter current is assumed to be 100%.
Period from when the output current drops below the
0 to 1s
Pr. 152 value until the zero current detection signal
(Y13) is output.
(1)
Output current detection
(Y12 signal, Pr. 150, Pr. 151)
The output current detection function can be used for
excessive torque detection, etc.
If the output current remains higher than the Pr. 150 setting
during inverter operation for longer than the time set in Pr.
151, the output current detection signal (Y12) is output from
the inverter's open collector or relay output terminal.
When the Y12 signal turns ON, the ON state is held for
approximately 100ms.
For the Y12 signal, set "12 (positive logic) or 112 (negative
logic)" in Pr. 190 to Pr. 192 (output terminal function selection)
and assign functions to the output terminal.
(2)
Zero current detection (Y13 signal, Pr. 152, Pr. 153)
If the output current remains lower than the Pr. 152 setting
during inverter operation for longer than the time set in Pr.
153, the zero current detection (Y13) signal is output from the
inverter's open collector or relay output terminal.
When the inverter's output current falls to "0", torque will not
be generated. This may cause a drop due to gravity when
the inverter is used in vertical lift application.
To prevent this, the Y13 signal can be output from the
inverter to close the mechanical brake when the output
current has fallen to "zero".
For the Y13 signal, set "13 (positive logic) or 113 (negative
logic)" in Pr. 190 to Pr. 192 (output terminal function selection)
and assign functions to the output terminal.