Test Point Diagram; Ftc4 (Controller Board) - Mitsubishi Electric EHSC-VM2B Service Manual

Hide thumbs Also See for EHSC-VM2B:
Table of Contents

Advertisement

10-7. Test point diagram

FTC4 (Controller board)

OUT10 (TBO.1 1-2)
Signal output (Boiler)
(non-voltage contact)
CNP1/OUT1 (TBO.1 3-4)
Water circulation pump1
(230V AC)
OUT2 (TBO.1 5-6)
Water circulation pump2
(Field supply) (230V AC)
OUT3 (TBO.1 7-8)
Water circulation pump3
(Field supply) (230V AC)
CNV1/OUT4 (TBO.1 9-11)
3-way valve/2-way valve1
(9-10: 230V AC)
OUT5 (TBO.1 12-14)
Mixing valve (Field supply)
(12-13[Open]: 230VAC)
(13-14[Close]: 230VAC)
OUT11 (TBO.2 1-2)
Signal output (Error) (230V AC)
OUT12 (TBO.2 3-4)
Signal output (Defrost) (230V AC)
OUT13 (TBO.2 7-8)
2-way valve2
(230V AC)
CNIH/OUT9 (TBO.2 9-10)
Signal output for immersion
heater (230V AC)
OUT8 (TBO.2 11-12)
Signal output for booster heater 2+
(230V AC)
CNBHT/BHT (TBO.2 13-14)
Thermostat input for
booster heater
CNBH
Signal output for booster heater
(1-3: heater1 230V AC)
(5-7: heater2 230V AC)
CNBC
Signal output for booster heater
protection (230V AC)
CNW12
Thermistor
(1-2: Flow water temp.)
(3-4: Return water temp.)
CN21
Thermistor (Ref. liquid temp.)
CN20
Thermistor
(Room temperature)
CN2F/IN2
(TBI.1 3-4)
IN3
Flow switch 1 input
(TBI.1 5-6)
Flow switch
2 input
IN1
IN4
(TBI.1 1-2)
(TBI.1 7-8)
Room thermo-
Demand
control input
stat 1 input
OCH532A
0
2
4
2
4
6
8
1
3
1
3
5
7
9
1
IN5
IN7
(TBI.1 9-10)
(TBI.1 13-14)
Outdoor ther-
Flow switch 3
mostat input
input
IN6
(TBI.1 11-12)
Room thermo-
stat 2 input
0
2
4
2
4
6
8
1
3
3
5
7
9
THW6
THWB1
(TBI.2 7-8)
(TBI.2 3-4)
Thermistor
Thermistor
(Zone1 flow
(Boiler flow
water temp. )
water temp.)
THWB2
THW8
(TBI.2 5-6)
(TBI.2 1-2)
Thermistor
Thermistor
(Boiler return
(Zone2 flow
water temp.)
water temp. )
67
F2
F1
6.3A/250V
6.3A/250V
THW9
CN22/RC(TBI.2 13-14)
(TBI.2 11-12)
Main controller
Thermistor
(10.4 - 13.7 V DC)
(Zone2 return
water temp. )
THW7
(TBI.2 9-10)
Thermistor
(Zone1 return
water temp. )
CN01
Power supply
(230V AC)
CN3C
Transmission
(Indoor/Outdoor)
(0 - 24V DC)
LED3
Transmission
(Indoor/Outdoor)
LED2
Power supply
(Main controller)
CNRF
Transmission (Indoor/
Wireless receiver)
(1-2: 11.5 - 13.2 V DC)
LED4
Reading or writing
data to SD card
CNPWM
Water circulation
pump 1
(2 - 3: 5V DC)
CN108
SD card
LED1
Power supply
(FTC4)
CNW5
Thermistor
(DHW tank water temp.)