6-5.Outdoor Control Board (Single Phase Type) - Toshiba HWS-803XWHM3-E Service Manual

Hide thumbs Also See for HWS-803XWHM3-E:
Table of Contents

Advertisement

6-5. Outdoor Control Board (Single phase Type)
HWS-803H-E
Power circuit protection
F100 (250 V, 3.15 A,
plastic case)
Case thermostat connector
CN609(Blue)
4-way valve connector
CN701(White)
Compressor ON
output connector
CN704(Blue)
Heater output connector
CN703(Grey)
External input connector
CN610(Yellow)
Special operation switches
SW801
SW804
Display change-over switches
SW800
SW803
Temperature sensor connectors
TL CN604(White)
TD CN603(White)
TO CN602(Yellow)
TE CN601(White)
TS CN600(White)
Alive, error display LEDs
D800
804(Yellow)
D805(Green)
PMV connector
CN710 (White)
Initialization switch
SW802
Hydro-outdoor communication signal LEDs
D503 (Green, Outdoor => Hydro)
D502 (Amber, Hydro => Outdoor)
Fan motor output
CN300 (White)
fuse
4-way valve protection
fuse
F700 (250 V, 3.15 A,
plastic case)
Connecting cable connector
Connecting cable protection fuse
Compressor output terminals
CN202
CN201
CN200
CN04(White)
F03 (250 V, 10 A)
33
Reactor connection connector
Electrolytic capacitors
Power circuit protection
fuse
F01 (250V, 25A)
Power supply connection lead
wires
P01(Red)
P02(White)
Earth lead wire
P09 (Black)