Fitting an external air break
• Refer to figure 17 when a rain water down pipe is used to dispose of
condensate.
• An air break must be installed in the 43mm pipe work, between the
boiler condensate outlet and the drainpipe, outside the property, to
avoid flooding during adverse weather conditions.
2
1
9
21.5mm Ø min
Fig. 17 Disposal into a rainwater down pipe
Condensate drainage pipe can be run above or below
ground.
Where the pipe terminates over an open drain or gully, the pipe should
terminate below the grating level, but above water level, in order to
minimise "wind chill" at the open end.
The use of a drain cover (such as those used to prevent blockage by
leaves) may offer further protection from wind chill.
Pipe drainage will be improved if the end is cut at 45° as opposed to a
straight cut.
21.5mm Ø min
1
9
2
Fig. 18 External disposal
21.5mm Ø min
1
2
Fig. 19 Condensate pump to external disposal
Greenstar Danesmoor Utility
ErP
and Utility System
11
10
12
13
14
15
10
25mm min.
9
10
8
67206813284-07.1Wo
ErP
- 6 720 813 286 (2014/09)
Continued - Key to condensate illustrations
16
100mm Ø minimum plastic pipe
17
Drainage holes
18
Limestone chippings (25kg min.)
19
Bottom of sealed tube
4.5.3

Soak away

• The condensate drainage pipe may be run above or below the ground
to the soak away. The examples shown on this page run above
ground.
• The soak away must use a 100mm Ø plastic tube with two rows of
three 12mm holes on 25mm centres and 50mm from the bottom of
the tube. The holes must face away from the house.
• The tube must be filled with and surrounded by at least 100mm of
limestone chippings to a depth of 400mm.
Minimum hole size for the condensate soak away must be
400mm deep by 300mmØ .
In situations where there are likely to be extremes of temperature or
exposure, the use of a proprietary trace-heating system for external pipe
work, incorporating an external frost thermostat, should be considered.
If such a system is used, the requirement to use 32mm pipe does not
apply. However, all other guidance above and the instructions for the
trace heating system, should be closely followed.
NOTICE: Unheated internal areas.
▶ Internal pipe runs in unheated areas such as lofts,
basements and garages should be treated as
external runs and insulate as necessary.
21.5mm Ø min
1
9
2
16
17
Unsuitable for clay soil types.
Fig. 20 Disposal to a soakaway
4.6

Pressure relief pipework

• The pressure relief discharge pipe (1) should be at least 15 mm
diameter copper pipe and run downwards away from the boiler and
discharge away from any electrical or other hazard, preferably to an
external drain or soakaway.
• Pipe (3) should be finished with a partial bend, near the outlet to face
the external wall (as shown) to help prevent freezing.
Pre-Installation
400mm min.
25mm min.
500mm min.
10
16
17
18
19
67206813284-05.1Wo