Connecting To Gas Supply - Barbeques Galore BVSR18 Owner's Manual

Table of Contents

Advertisement

INSTALLATION
Continued
VENTING SPECIFICATIONS FOR
INSTALLATION
The fireplace chimney flue and vent must be drafting properly. To
check the vent for proper drafting: Light a tightly rolled newspaper
on one end and place it at the inside front edge of the fireplace.
Observe the smoke and be sure the vent is properly drawing it up the
chimney. If the smoke spills out into the room, extinguish the flame
and remove any obstruction until proper venting is achieved.
The chimney flue damper must be fixed open to provide a minimum of
64 sq. in. of free air opening during operation of this log set. A multi-
purpose damper clamp is provided to fix the damper in position.
INSTALLING DAMPER CLAMP
Secure the damper stop clamp provided to the leading edge of the
damper as shown in Figure 3. If for any reason this clamp doesn't
work on your fireplace, another suitable clamp or permanent stop
must be installed, or the damper blade must be cut or removed.
Damper Clamp
Damper
Manufactured
Masonry Fireplace
Fireplace
Figure 3 - Attaching Damper Clamp

CONNECTING TO GAS SUPPLY

WARNING: A qualified service person must con-
nect log set to gas supply. Follow all local codes.
Installation Items Needed
Before installing log set, make sure you have the items listed below.
• piping (check local codes)
• sealant (resistant to LP gas)
• equipment shutoff valve
• test gauge connection
• adjustable (crescent) wrench or pliers
• sediment trap
• tee joint
• pipe wrench
901746-01D
Damper
Clamp
Damper
Damper
Venting Specifications for Installation
Installing Damper Clamp
Connecting to Gas Supply
CAUTION: Use only new, black iron or steel pipe.
Internally-tinned copper tubing may be used in certain
areas. Check your local codes. Use pipe of 1/2" diam-
eter or greater to allow proper gas volume to log set. If
pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from log set (see Figure 4).
IMPORTANT: Install equipment shutoff valve in an accessible
location. The equipment shutoff valve is for turning on or shutting
off the gas to the appliance.
Apply pipe joint sealant lightly to male NPT threads. This will
prevent excess sealant from going into pipe. Excess sealant in pipe
could result in a clogged burner injector.
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install sediment trap in supply line as
shown in Figure 4. Locate sediment trap where it is within reach for
cleaning. Install in piping system between fuel supply and heater.
Locate sediment trap where trapped matter is not likely to freeze. A
sediment trap traps moisture and contaminants. This keeps them
from going into log set controls. If sediment trap is not installed or
is installed wrong, log set may not run properly.
Approved Flexible Gas Hose
(if allowed by local codes)
3" Minimum
Cap
Sediment Trap
Figure 4 - Gas Connection
* Purchase the optional CSA design-certified equipment shutoff
valve from your dealer. See Accessories, page 15.
** Minimum inlet pressure for purpose of input adjustment.
INSTALLATION
CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*
From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)
Pipe
Tee
Nipple
Joint
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bvsr24Bvdr18Bvdr24Bvdr30Bflr18Bflr24

Table of Contents