Vitodens 200 Accessories
Accessories for Vitodens 200
The temperature sensor connection [TS]
located at the top of the low-loss header
ensures low return temperatures to the
Vitodens 200 boiler at all times, increasing
operational efficiency.
In addition, the low-loss header helps
eliminate air and debris [D] from the heating
system.
See figures on the right for an illustration of
the principle of operation.
The low-loss header is available in the
following sizes. Select the size based on the
maximum system flow rate of your
application.
Model No.
Max. system flow rate
Type 80/50
17.6 GPM / 4 m
Type 120/80
35.2 GPM / 8 m
*1
Type 160/80
44 GPM / 10 m
Type
80 GPM / 18 m
*1
200/120
*1
Product does not look exactly as
illustrated.
30
(continued)
BS
TS
BY
3
/h
3
/h
3
/h
3
/h
BR
Low-loss header design
(Type 80/50 or 120/80)
T1
V
primary
T2
Principle of Operation
SC
AB
SW
SS
SR
D
DV
T3
V
secondary
T4
Legend
AB Air Bleed
BR Boiler Return
BS Boiler Supply
BY Bypass with laminar flow
D
Debris and/or air
DV Drain Valve
SC Sensor Cable
SR System Return
SS System Supply
TS Temperature Sensor
SW Sensor Well
T1 Boiler supply temperature
T2 Boiler return temperature
T3 System supply temperature
T4 System return temperature
V
Boiler circuit flow rate
primary
V
Heating circuit flow rate
secondary
Q
Heat supplied by boiler
primary
Q
Heat consumed by system
secondary
V
< V
primary
secondary
T1 > T3
T2 = T4
Q
= Q
primary
secondary