5
Dimensional drawing & centre of gravity

5 - 1 Dimensional drawing for standard panel

FCQ35-71C8
950
Piping side
Drain side
VIEW A
840
55
340
280
330
Hanging bolt
4 x M8~M10
NOTES
1
Location of the nameplates
- Unit body: on the control box cover.
- Decoration panel: on the panel frame at the motor side under the corner cover
2
When installing an optional accessory, refer to the installation drawings.
- For the fresh air intake kit an inspection port is necessary
3
In case of using an infrared remote control, this position will be a signal
receiver. Refer to the drawing of the infrared remote control for more detail.
FCQ(H)100-140C8
Piping side
Drain side
View A
Hanging bolt
NOTE
1
Location of the nameplates - Unit body: on the control box - Decoration panel: on the panel frame at the motor side under the corner cover
2
When installing an optional accessory, refer to the installation drawings
For the fresh air intake kit an inspection port is necessary
3
In case of using a wireles remote control, this position will be a signal receiver. Refer to the drawing of the wireless remote control for more detail.
4
Make sure the spacing between the ceiling and the cassette is no more than 35mm. Max cailing opening: 910mm.
5
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air is inducted into the ceiling, an additionalinsulation is required (polyethylene foam,
thickness 10mm or more).
• Indoor Units • R-410A • FCQ-C8VEB
860-910 (Ceiling opening)
300 or less
710 (Suspension position
420
3
SEE NOTE
420
55
55
840
35
4
SEE NOTE
4
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. MAX ceiling opening: 910mm.
5
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air
is inducted into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
6
Please respect the distances as shown on the figure
(Ceiling opening)
300 or less
(Suspension position)
see note 3
see note 4
• Split Sky Air • Indoor Units
Nr
4
SEE NOTE
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
10
Knock out hole
SEE NOTE
55
35
4
SEE NOTE
see note 4
Please respect the distances as shown on figure below
see note 4
Name
Description
ø A flare connection
ø B flare connection
VP25 (O.D. ø 32 /I.D. ø 25)
O.D. ø 32 /I.D. ø 26
MODEL
A
213
FCQ35
6.35
FCQ50-60
6.35
FCQ71
9.52
VIEW B
VENTILATOR
OTHER UNIT
EXTERNAL
6
SURFACE
LIGHT
1500 or more
2000 or more
4000 or more
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
(*) In case a discharge opening is closed with the 'sealing member' option,
the distance of 1500mm can be reduced to 500mm on the closed side.
3TW28834-1B
Item
Name
Remark
1
Liquid pipe connection
ø9.52 (Flare connection)
2
Gas pipe connection
ø15.90 (Flare connection)
3
Drain pipe connection
VP25 (ODø32, IDø25)
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
ODø32, IDø25
10
Knock out hole
View B
External
Other unit
Ventilator
surface
light
1500 or more
2000 or more
4000 or more
1500 mm
or more (*)
200 mm
or more
1500 mm
1500 mm
or more (*)
or more (*)
200 mm
1500 mm
or more
or more (*)
(*) In case a discharge opening is closed with
the "sealing member" option, the distance of
1500 mm can be reduced to 500 mm on the
closed side.
3TW28914-1C
B
9.52
12.7
15.9
7

Hide quick links: