5
Dimensional drawing & centre of gravity
5 - 2 Dimensional drawing for auto cleaning panel
FCQ100-140C8VEB
Piping side
Drain side
VIEW A
Hanging bolt
NOTES
1.
Location of the nameplates:
•
Unit body: on the control box.
•
Decoration panel: on the panel frame at the motor side under the
corner cover
2.
When installing an optional accessory, refer to the installation drawings.
•
For the fresh air intake kit an inspection part is necessary
3.
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. Max. ceiling opening: 910mm
4.
When the conditions exceed 30°C and RH 80% in de ceiling or fresh
air is included into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
8
• Indoor Units • R-410A • FCQ-C8VEB
860~910 (Ceiling opening)
710 (Suspension position)
300 or less
See note 3
5.
Installation direction
Piping
• Split Sky Air • Indoor Units
See note 3
6.
Please respect the distances as shown on fi gure below
(*1) Does not count for build in light
(*2) Space needed to enter with vacuum-cleaner tube.
(*3) Keep the exhaust of decoration panel free.
See note 3
200mm or
more (*4)
1500mm or
more (*4)
Dust
opening
(*4) In case a discharge opening is closed with the 'sealing member' option,
Piping
Suction
grill
Nr
Name
Description
1
Liquid pipe connection
Ø9.52 fl are connection
2
Gas pipe connection
Ø15.90 fl are connection
3
Drain pipe connection
VP25 (O.D.Ø32, I.D. Ø25)
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
O.D.Ø32, I.D. Ø26
10 Knock out hole
VIEW B
Ventilator
Other unit
External
surface
light (*1)
256
1500 or more
2000 or more
4000 or more
1500mm or
more (*4)
1500mm or
more (*4)
200mm or
more (*4)
1500mm or
more (*4)
the distance of 1500mm can be reduced to 500 mm on the closed side.
3TW32524-1