6, Electrical work
®
@
÷
/
®
L_ Terminal board cover
(_ Screw
@ Band
@ Printed circuit board cover
L_ Right side panel
Coupler connector
Terminal board for remote con-
troller (for PKA-A.FA)
_H_ Terminal board for control lines
from the outdoor unit
(_) Power supply wiring & connec-
tion wiring
@ Cord clamp
Bush (Purchased
locally)
Lock nut (Purchased locally)
Conduit plate
@ Connector (Purchased locally)
_P)Conduit (Purchased locally)
6.1. Indoor unit (Fig. 6-1)
(_) Remove
the right
side panel.
To do this,
remove
the screws
on the mower and right sides.
Remove
the securing
screw
on the terminal
board
cover
to take away
the cover.
®
Connect
the power,
control
line. (3 x 2.5 mm 2 2 poler).
This
cables
shaft not
lighter
than
polychloroprene
sheathed
flexibme
cord.
(design
245 mEC 57)
Fix power
source
wiring
to control
box using
buffer bushing
for tensile
force.
(PG connection
or the like,)
• Since
the electric
box may need to be pulled
out for servicing
or other
occasions,
wires
must have enough
slack.
Class
3 grounding
work must be conducted
(grounding
wire size: 2.5 mm 2 or more).
After
wiring
is completed,
reinstall
the parts in the reverse
order
of removal.
z_ Warning:
Wiring
should
be done
so that
the power
mines are not subject
to tension.
Oth=
erwise,
heat may
be generated
or fire may
occur.
© @
®
Fig. 6=1
6,1,1,
indoor
unit
power supplied
from outdoor
unit (A=control
application)
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
(_)
(_
@ Outdoor unit power supply
[-7 I
(_) Wiring circuit breaker or isolating switch
I
!
@ Outdoor unit
(_)
i
_ Indoor unit/outdoor unit connecting cords
J_!
(_) Remot ....
troller (On,y for PKA-A.FA)
', _
_ Indoor unit
h(_)'i
_
_i
¢ Ind .....
it earth
@
* Affix
a label
A that is included
with the manuams near each wiring
diagram
for the indoor
and outdoor
units.
Indoor unit model
PKA
Minimum circuit ampacity
1A
Maximum rating of overcurrent protective device
15A
•_
Indoor unit-Outdoor unit
"1
3 x AWG16 (polar)
#x
:_
ndoor unit earth
1 x Min. AWG16
Remote controller-Indoor
unit
*2
2 x AWG22 (Non-polar)
Indoor unit-Outdoor unit $1-$2
*3
AC 208/230 V
..=_
=
Indoor unit-Outdoor unit $2-$3
*3
DC24 V
LS_
Remote controller-Indoor
unit
*3
DC12 V
"1. Max. 50 m, 165ft
*2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max. 500 m, 1500 ft <Only for PKA-A-FA>
*3. The figures are NOT always against the ground.
$3 terminal has DC 24 V against S2 terminal. However between S3 and Sl, these terminals are not electrically insulataed by the transformer or other device.
Notes:
1. Wiring size must comply with the applicable
local and national code.
2. Use copper supply wires.
3. Use wires rated 300V or more for the power supply cables and the indoor unit/outdoor
unit connecting cables.
4. Install an earth longer than other cables.
7