EEDEN08-100 technical data FVQ-B Split Sky Air...
Page 2
“ The present publication is drawn up by way of information only Het ISO14001 assures an effective ufacturer of air conditioning equip- and does not constitute an offer binding upon Daikin Europe N.V.. environmental management system in order to ment, compressors and refrige- Daikin Europe N.V.
Page 3
EEDEN08-100 technical data FVQ-B Split Sky Air...
• Indoor Units • R410A • FVQ-B Features U n i o o r I n d F V Q R 4 1 • Ideal solution for shops, restaurants or offices without false ceilings • Quiet operation: down to 35 dBA sound pressure level (71 class) •...
• Indoor Units • R410A • FVQ-B Specifications 2-1 FOR INDOOR UNITS ONLY FVQ71BV1B FVQ100BV1B FVQ125BV1B Nominal input Cooling 0.175 0.320 0.365 (Indoor only) Heating 0.175 0.320 0.365 2-2 TECHNICAL SPECIFICATIONS FVQ71BV1B FVQ100BV1B FVQ125BV1B Casing Colour White Dimensions Packing Height...
Page 7
• Indoor Units • R410A • FVQ-B Specifications 2-2 TECHNICAL SPECIFICATIONS FVQ71BV1B FVQ100BV1B FVQ125BV1B Standard Item Operation manual Accessories Installation manual Bracket for installation Through hole protecting rubber Bush Insulation for fitting Control panel patch plate Remote control lid Clamps...
• Indoor Units • R410A • FVQ-B Options Name of option \ Model name FVQ71∼100∼125BV1B Replacement long-life filter KAFJ95L160 Set back time clock BRC15A51 Central remote control z 1 DCS302CA51 Unified ON/OFF control z 1 DCS301BA51 Schedule timer z 1 DST301BA51 Intelligent touch controller z 1 DCS601C51...
• Indoor Units • R410A • FVQ-B Dimensional drawing & centre of gravity 5 - 1 Dimensional drawing unit (mm) FVQ71B View A This model to be fixed with fixture as shown below. In case of fixing it at the bottom (In case vibration resistance is required, fix it at both the bottom and the rear.)
• Indoor Units • R410A • FVQ-B Piping diagram Indoor heat exchanger Field piping J A C1220T-0 To outdoor unit Field piping J B C1220T-0 Indoor unit Model FVQ71,100,125BV1B 15.9 4D037995H • Split Sky Air • Indoor Units...
• Indoor Units • R410A • FVQ-B Wiring diagram 7 - 1 Wiring diagram Notes Indoor unit : Terminal : Connector To outdoor unit : Field : Short circuit connector wiring Control panel 2 In case using central remote controller, connect it NORM.EMG.
• Indoor Units • R410A • FVQ-B Wiring diagram 7 - 2 External connection diagram FVQ-B Y1, Model TAL, Model V1, Model VAL, Model TAL, Model Power supply Power supply Power supply Power supply Power supply 1∼50Hz 3N∼50Hz 1∼60Hz 3∼60Hz 3N∼60Hz 220V-240V 380V-415V...
• Indoor Units • R410A • FVQ-B Sound data 8 - 1 Sound pressure spectrum FVQ71B FVQ100B High High approximate threshold approximate threshold hearing for continuous hearing for continuous noise noise Octave band center frequency (Hz) Octave band center frequency (Hz) NOTES NOTES Operation noise differs with operation and...