Electric Installation - Keltech CNA-36 Installation Manual

Cna-series tankless heater
Table of Contents

Advertisement

Installation
3

Electric Installation

WARNING All Keltech heaters must be fused in accordance with National Electric Code (NEC) for the
full load amperage listed on the nameplate rating for each heater.
WARNING Failure to properly ground the unit(s) per the National Electric Code could result in injury or
death.
A
Open enclosure door .
NOTICE! Any option that requires field wiring
must be done with 600V cable per
the schematic that was shipped with
the heater.
NOTICE! Use a 4-core cable or multi-stranded
machine tool wire from an approved
isolating 3-pole switch or circuit
breaker.
NOTICE! Make sure the electrical cable is the
correct size to carry 100% of the full
load current. See table for proper
wire sizes.
Using a hole punch, cut a hole the
proper size for conduit connection;
B
large enough for the wire size for each
heater . The connectors need to be rated
NEMA4/4X to ensure proper sealing of
the enclosure . .
C
Run wires through the appropriate size
conduit .
Connect wires to the system terminal
D
block or fused disconnect inside the
enclosure .
E
Connect the ground wire to the stud
provided with the "Ground" label beneath it .
Keltech • 215-1814 Rev. C; ECN 150010
CNA & CNAR ELECTRICAL SPECIFICATIONS FOR HEATER**
Model
Voltage
CNA-363/600D
600
CNA-543/600D
600
CNA-633/600D
600
CNA-723/600D
600
CNA-1083/600D
600
CNA-1263/600D
600
CNA-1443/600D
600
CNA-363/480D
480
CNA-543/480D
480
CNA-633/480D
480
CNA-723/480D
480
CNA-1083/480D
480
CNA-1263/480D
480
CNA-1443/480D
480
CNA-363/415D
415
CNA-543/415D
415
CNA-633/415D
415
CNA-723/415D
415
CNA-1083/415D
415
CNA-1263/415D
415
CNA-1443/415D
415
CNA-363/400D
400
CNA-543/400D
400
CNA-633/400D
400
CNA-723/400D
400
CNA-1083/400D
400
CNA-1263/400D
400
CNA-1443/400D
400
CNA-363/380D
380
CNA-543/380D
380
CNA-633/380D
380
CNA-723/380D
380
CNA-1083/380D
380
CNA-1263/380D
380
CNA-1443/380D
380
* Based on the NEC Table 310 .15 for 75°C insulated wire @ 30°C Ambient
** CNAR (reverse models) electrical specifications are same as CNA heater
models .
7/13/2015
CNA-Series Tankless Heater
Min Wire
Amps
kWatts
Size
35
36
8 AWG*
52
54
6 AWG*
61
63
4 AWG*
69
72
4 AWG*
104
108
2 AWG*
121
126
1 AWG*
139
144
1/0 AWG*
43
36
6 AWG*
65
54
4 AWG*
76
63
4 AWG*
87
72
3 AWG*
130
108
1 AWG*
152
126
1/0 AWG*
174
144
2/0 AWG*
38
27
8 AWG*
56
40
6 AWG*
65
47
4 AWG*
75
54
4 AWG*
113
81
2 AWG*
131
94
1 AWG*
150
108
1/0 AWG*
36
25
8 AWG*
53
37
6 AWG*
64
44
4 AWG*
72
50
4 AWG*
108
75
2 AWG*
126
87
1 AWG*
144
100
1/0 AWG*
35
23
8 AWG*
50
33
6 AWG*
59
39
6 AWG*
68
45
4 AWG*
103
68
2 AWG*
120
79
1 AWG*
137
90
1/0 AWG*
7

Advertisement

Table of Contents
loading