Download Print this page

Trane 4DCY4024 Product Data page 6

Packaged convertible dual fuel 14 seer 2-5 ton, 60-120 mbtu
Hide thumbs Also See for 4DCY4024:

Advertisement

MODEL
RATED Volts/PH/Hz
Performance Cooling BTUH
Indoor Airflow (CFM)
Power Input (KW)
EER/SEER(BTU/Watt-Hr.)
Sound Power Rating [dB(A)]7
HP Heating Performance
(High Temp.)BTUH / COP
Power Input (KW)
(Low Temp.) BTUH / COP
Power Input (KW)
HSPF (BTU / Watt-Hr.)
Gas Heating Performance
(High) Input BTUH
Capacity BTUH
Temp. Rise — Min/Max (°F)
(Low) Input BTUH
Capacity BTUH
AFUE
Type of Gas 
Gas Pipe Size (in.)
POWER CONN.—V/PH/HZ
Min. Brch. Cir. Ampacity
Fuse Size — Max. (amps)
Fuse Size — Recmd. (amps)
COMPRESSOR
Volts/Ph/Hz
R.L. Amps — L.R. Amps
OUTDOOR COIL — TYPE
Rows/F.P.I.
Face Area (sq.ft.)
Tube Size (in.)
Refrigerant Control
INDOOR COIL — TYPE
Rows/F.P.I.
Face Area (sq.ft.)
Tube Size (in.)
Refrigerant Control
Drain Conn. Size (in.)
OUTDOOR FAN — TYPE
Dia. (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g. 7
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
INDOOR FAN — TYPE
Dia x Width (in.)
Drive/No. Speeds
CFM @ 0.0 in. w.g.
SEE FAN PERFORMANCE TABLE
Motor — HP/R.P.M.
Volts/Ph/Hz
F.L. Amps/L.R. Amps
COMBUSTION FAN — TYPE
Drive/No. Speeds
Motor — HP/R.P.M. (High/Low)
Volts/Ph/Hz
FLA
FILTER / FURNISHED
Type Recommended
Recmd. Face Area (sq. ft.)
REFRIGERANT / Charge (lbs.)
DIMENSIONS
Crated (in.)
WEIGHT / Shipping / Net (lbs.)
1 Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on AHRI
Standard 210/240.
2 All models are U L Listed. Ratings shown are for elevations up to 2000 ft. For higher elevations reduce ratings at a
rate of 4% per 1000 ft. elevation.
3 Convertible to LPG.
4 This value is approximate. For more precise value, see Unit Nameplate.
5 Based on U.S. Government Standard Tests.
6 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent
filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C.
7 Sound Power values are not adjusted for AHRI 270-95 tonal corrections.
8 Standard Air — Dry Coil — Outdoor.
General Data
4DCY4036B3075A
208-230/3/60
36000
1185
3.28
11.4 / 14.0
69
32400 / 3.5
2.7
20600 / 2.36
2.6
8.0
75000
60500
30 / 60
56250
48400
80.0
NATURAL
1/2
208-230/3/60
18.5
25
25
SCROLL
208-230/3/60
10.4 / 73
SPINE-FIN
2 / 24
15.49
3/8
EXPANSION VALVE
PLATE FIN
4 / 15
3.54
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
23.4
DIRECT / 1
3270
1/5 / 830
208-230/1/60
1.1 / 1.9
CENTRIFUGAL
10 X 10
DIRECT / VARIABLE
1/2 / VARIABLE
200-230/1/60
4.3 / 4.3
CENTRIFUGAL
DIRECT / 2
1/45 / 2800/1500
208-230/1/60
0.34
NO
THROWAWAY
4
R410A / 7.4
H X W X L
47.86 / 44.5 / 52.03
488 / 392
6
4DCY4042C1090A
208-230/1/60
42000
1380
3.50
12.0 / 14.0
74
38000 / 3.45
3.23
23400 / 2.32
2.96
8.0
90000
72900
30 / 60
72000
58320
81
NATURAL/LP
1/2
208-230/1/60
30.8
45
45
SCROLL
208-230/1/60
17.9 / 112
SPINE-FIN
2 / 24
18.01
3/8
EXPANSION VALVE
PLATE FIN
3 / 15
5
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
4440
1/4 / 825
208-230/1/60
1.5 / 3.4
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERFORMANCE TABLE
3/4 / VARIABLE
208-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/20 / 3350/2600
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A / 8.2
H X W X L
47.86 / 47.4 / 61.75
653 / 525
4DCY4048C1090B
208-230/1/60
47500
1470
3.96
12.0 / 14.0
73
45000 / 3.5
3.77
26800 / 2.3
3.44
8.0
90000
72900
30 / 60
72000
58320
81
NATURAL/LP
1/2
208-230/1/60
33.9
50
50
SCROLL
208-230/1/60
20.5 / 109
SPINE-FIN
2 / 24
18.01
3/8
EXPANSION VALVE
PLATE FIN
3 / 15
5.0
3/8
EXPANSION VALVE
3/4 FEMALE NPT
PROPELLER
28.2
DIRECT / 1
4450
1/4 / 825
208-230/1/60
1.4 / 3.5
CENTRIFUGAL
11 X 10
DIRECT / VARIABLE
SEE FAN PERFORMANCE TABLE
3/4 / VARIABLE
200-230/1/60
6.8 / 6.8
CENTRIFUGAL
DIRECT / 2
1/20 / 3350/2600
208-230/1/60
0.34
NO
THROWAWAY
5.3
R410A / 7.75
H X W X L
47.86 / 47.4 / 61.75
653 / 525

Advertisement

loading

This manual is also suitable for: