Condensate Trap Locations; Condensate Trap With Optional Overflow Switch; Coil Using A Separate Drain - Lennox EL296UH045XE36B Unit Information

El296uhe series
Hide thumbs Also See for EL296UH045XE36B:
Table of Contents

Advertisement

on the condensate trap and line. Heating cable kit is
available from Lennox in various lengths; 6 ft. (1.8m) -
kit no. 26K68; 24 ft. (7.3m) - kit no. 26K69; and 50 ft.
(15.2m) - kit no. 26K70.

CONDENSATE TRAP LOCATIONS

(Unit shown in upflow position with remote trap)
Field ProvidedVent
Min. 1" Above Condensate
Drain Connection
1" Min.
2" Max.
*5' max.
PV C PipeOnly
*Piping from furnace must slope down a minimum of
1/4" per ft. toward trap.
FIGURE 43
EL29UHE
With

Coil Using A Separate Drain

Field Provided Vent
(1" min. 2" max. above
condensate connec­
tion)
Condensate
Drain Connection
FIGURE 44
T o Drai n
Evaporator
Evaporator drain
line required
Page 41

Condensate Trap With Optional Overflow Switch

From Evaporator Coil
HorizontalFurnace4" Min. to 5" Max.above
Optional
FIGURE 45
condensatedrain connection)
FurnaceCondensate
Drain Connection