Iv-Heating System Service Checks - Lennox G27M series Unit Information

Hide thumbs Also See for G27M series:
Table of Contents

Advertisement

IV–HEATING SYSTEM SERVICE CHECKS
A–A.G.A. / C.G.A. Certification
All G27M units are A.G.A. / C.G.A. design certified with-
out modifications. Refer to the G27M Installation
Instruction for Information.
B–Gas Piping
Gas supply piping should not allow more than 0.5"W.C.
drop in pressure from unit with gas valve off and with
unit operating at second–stage heat (high fire). Supply
gas pipe must not be smaller than unit gas connection.
Refer to table 6 if pressure drop exceeds 0.5"W.C. or if
gas piping is suspect. Do not operate furnace below
nameplate minimum line pressure.
C–Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off
the main shut-off valve and disconnect the main
power to unit. These controls should be properly
labeled by the installer.
When pressure testing gas lines, the gas valve must be
disconnected and isolated. Gas valves can be damaged
if subjected to more than 0.5psig (14" W.C.). See figure
16 . If the pressure is equal to or less than 0.5psig
(14"W.C.), use the manual shut–off valve before
pressure testing to isolate furnace from gas supply.
Nominal
Internal
Iron Pipe Size
I
Pi
Si
Di
Diameter
–Inches(mm)
–Inches(mm)
1/4
.364
(6.35)
(9.246)
3/8
.493
(9.53)
(12.522)
1/2
.622
(12.7)
(17.799)
3/4
.824
(19.05)
(20.930)
1
1.049
(25.4)
(26.645)
1–1/4
1.380
(31.75)
(35.052)
1–1/2
1.610
(38.1)
(40.894)
2
2.067
(50.8)
(52.502)
2–1/2
2.469
(63.5)
(67.713)
3
3.068
(76.2)
(77.927)
4
4.026
(101.6)
(102.260)
NOTE–Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
TABLE 6
GAS PIPE CAPACITY – FT
10
20
30
(3.048)
(6.096)
(9.144)
43
29
24
(1.13)
(.82)
(.68)
95
65
52
(2.69)
(1.84)
(1.47)
175
120
97
(4.96)
(3.40)
(2.75)
360
250
200
(10.19)
(7.08)
(5.66)
680
465
375
(919.25)
(13.17)
(10.62)
1400
950
770
(39.64)
(26.90)
(21.80)
2100
460
1180
(59.46)
(41.34)
(33.41)
3950
2750
2200
(111.85)
(77.87)
(62.30)
6300
4350
3520
(178.39)
(123.17)
(99.67)
11000
7700
6250
(311.48)
(218.03)
(176.98)
23000
15800
12800
(651.27)
(447.39)
(362.44)
Page 12
GAS PIPING TEST PROCEDURE
MANUAL MAIN SHUT–OFF VALVE
GAS VALVE WILL NOT HOLD TEST
PRESSURE IN EXCESS OF 0.5
PSIG (14"W.C.)
GAS VALVE
When checking piping connections for gas leaks, use
preferred means. Kitchen detergents can cause harmful
corrosion on various metals used in gas piping. Use of a
specialty gas leak detector is strongly recommended. It
is available through Lennox under part number
31B2001. See Corp. 8411–L10, for further details.
Do not use matches, candles, flame or any other source
of ignition to check for gas leaks.
D–Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
inlet pressure tap (field provided). See figure 16. Check
gas line pressure with unit firing at maximum rate. Low
pressure may result in erratic operation or underfire. High
pressure can result in permanent damage to gas valve or
overfire. For natural gas units, operating pressure at unit
gas connection must be a minimum of 5.0" W.C. but no
more than 13.0"W.C. at any time.
3
/HR (kL/HR)
Length of Pipe–Feet(m)
40
50
60
(12.192)
(15.240)
(18.288)
20
18
16
(.57)
(.51)
(.45)
45
40
36
(1.27)
(1.13)
(1.02)
82
73
66
(2.32)
(2.07)
(1.87)
170
151
138
(4.81)
(4.28)
(3.91)
320
285
260
(9.06)
(8.07)
(7.36)
660
580
530
(18.69)
(16.42)
(15.01)
990
900
810
(28.03)
(25.48)
(22.94)
1900
1680
1520
(53.80)
(47.57)
(43.04)
3000
2650
2400
(84.95)
(75.04)
(67.96)
5300
4750
4300
(150.07)
(134.50)
(121.76)
10900
9700
8800
(308.64)
(274.67)
(249.18)
CAP
FIELD PROVIDED
LINE PRESSURE TAP
FIGURE 16
70
80
90
(21.336)
(24.384)
(27.432)
15
14
13
(.42)
(.40)
(.37)
33
31
29
(.73)
(.88)
(.82)
61
57
53
(1.73)
(1.61)
(1.50)
125
118
110
(3.54)
(3.34)
(3.11)
240
220
205
(6.80)
(6.23)
(5.80)
490
460
430
(13.87)
(13.03)
(12.18)
750
690
650
(21.24)
(19.54)
(18.41)
1400
1300
1220
(39.64)
(36.81)
(34.55)
2250
2050
1950
(63.71)
(58.05)
(55.22)
3900
3700
3450
(110.43)
(104.77)
(97.69)
8100
7500
7200
(229.36)
(212.37)
(203.88)
100
(30.480)
12
(.34)
27
(.76)
50
(1.42)
103
(2.92)
195
(5.52)
400
(11.33)
620
(17.56)
1150
(32.56)
1850
(52.38)
3250
(92.03)
6700
(189.72)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents