Test Run; Customer Guidance; Error Codes - Fujitsu ASU12RLS3 Installation Instructions Manual

Indoor unit wall mounted type
Hide thumbs Also See for ASU12RLS3:
Table of Contents

Advertisement

Setting
Function number
value
00
01
02
03
04
05
06
07
08
92
93
(For cooling)
(For heating)
09
10
11
12
13
14
15
16
17
Setting record
 Record any changes to the settings in the following table.
Setting
Heat Insulation condition (building insula-
tion)
Room temperature control for indoor unit
sensor
Room temperature control for wired remote
controller sensor
After completing the Function Setting, be sure to turn off the power and turn it on again.

14. TEST RUN

Check items
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do air fl ow direction louvers operate normally?
(4) Is the drain normal?
(5) Do not have an abnormal noise and vibration during operation?
Do not operate the air conditioner in test run for a long time.
[Operation method]
 For the operation method, refer to the operating manual.
 The outdoor unit, may not operate, depending on the room temperature. In this
case, keep on pressing the MANUAL AUTO button of the indoor unit for more than
10 seconds. The operation indicator lamp and timer indicator lamp will begin to fl ash
simultaneously during cooling test run. Then, heating test run will begin in about three
minutes when HEAT is selected by the remote control operation. (Please follow the
operating manual for remote control operation.)
To end test operation, press the remote controller START/STOP button.
(When the air conditioner is running by pressing the TEST RUN button, the
OPERATION Lamp and TIMER Lamp will simultaneously fl ash slowly.)
[Using the wired remote control] (Option)
For the operation method, refer to the operating manual.
(1) Stop the air conditioner operation.
(2) Press the MODE button and the FAN button simultaneously for 2 seconds or more to
start the test run.
(3) Press the START/STOP button to stop the test run.
Setting description
No correction 0.0°F (0.0°C)
No correction 0.0°F (0.0°C)
-1°F (-0.5°C)
-2°F (-1.0°C)
-3°F (-1.5°C)
More
-4°F (-2.0°C)
Cooling
Less
-5°F (-2.5°C)
Heating
-6°F (-3.0°C)
-7°F (-3.5°C)
-8°F (-4.0°C)
+1°F (+0.5°C)
+2°F (+1.0°C)
+3°F (+1.5°C)
Less
+4°F (+2.0°C)
Cooling
More
+5°F (+2.5°C)
Heating
+6°F (+3.0°C)
+7°F (+3.5°C)
+8°F (+4.0°C)
Setting Value
Cooling
Heating
Cooling
Heating
Test run display

15. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature adjustment, timer, air
fl ow switching, and other remote control unit operations.
(2) Air fi lter removal and cleaning, and how to use the air louvers.
(3) Give the operating manual to the customer.

16. ERROR CODES

If you use a wireless remote controller, the lamp on the photo detector unit will output error
codes by way of blinking patterns. If you use a wired remote controller, error codes will ap-
pear on the remote control display. See the lamp blinking patterns and error codes in the
table. An error display is displayed only during operation.
Error display
OPERATION
TIMER
ECONOMY
lamp
lamp
lamp
(green)
(orange)
(green)
(1)
(1)
(1)
(2)
(1)
(5)
(2)
(1)
(2)
(2)
(2)
(3)
(2)
(4)
(2)
(7)
(3)
(2)
(3)
(5)
(4)
(1)
(4)
(2)
(5)
(1)
(5)
(3)
(5)
(7)
(5)
(8)
(5)
(15)
(6)
(2)
(6)
(3)
(6)
(4)
(6)
(5)
(6)
(10)
(7)
(1)
(7)
(2)
(7)
(3)
Wired
remote
Description
controller
Error code
Serial communication error
Wired remote controller
communication error
Check run unfinished
Unit number or Refrigerant circuit
address setting error
[Simultaneous Multi]
Indoor unit capacity error
Combination error
• Connection unit number error
(indoor secondary unit)
[Simultaneous Multi]
• Connection unit number error
(indoor unit or branch unit)
[Flexible Multi]
Primary unit, secondary unit set-
up error [Simultaneous Multi]
Indoor unit PCB model
information error
Manual auto switch error
Room temp. sensor error
Indoor unit Heat Ex. Middle temp.
sensor error
Indoor unit fan motor error
Drain pump error
Damper error
Intake grille error
Indoor unit error
Outdoor unit main PCB model
information error or
communication error
Inverter error
Active filter error, PFC circuit er-
ror
Trip terminal L error
Display PCB microcomputers
communication error
Discharge temp. sensor error
Compressor temp. sensor error
Outdoor unit Heat Ex. liquid
temp. sensor error
En-11