Troubleshooting
Fault messages on the display
Displayed
System characteris-
fault code
tics
51
No DHW heating
58
No DHW heating
59
No DHW heating
A9
Control mode without
OpenTherm device
b0
Burner blocked
b8
Burner blocked
E3
Burner in a fault
state
E5
Burner blocked
F0
Burner blocked
F1
Burner in a fault
state
44
(cont.)
Cause
Short circuit, outlet
temperature sen-
sor
Lead break, cylin-
der temperature
sensor
Lead break, outlet
temperature sen-
sor
Communication
error, OpenTherm
device
Short circuit, flue
gas temperature
sensor
Lead break, flue
gas temperature
sensor
Fault in safety
chain.
Internal fault
Internal fault
Max. flue gas tem-
perature exceeded
Measures
Check the sensor (see
page 51).
Check the sensor (see
page 50).
Check the sensor (see
page 51).
Check connections and
cable; replace Open-
Therm device if required.
Check the sensor (see
page 53).
Check the sensor (see
page 53).
Check the temperature
limiter and connecting
leads (see page 52).
Check the control unit,
and replace if required.
Check the ionisation elec-
trode and connecting
cables.
Press "RESET" (see
page 46).
Replace control unit.
Check heating system fill
level. Check circulation
pump. Vent the system.
Press "RESET" (see
page 46).