Wiring - Honeywell TH8320R1003 Vision Pro 8000 Product Data

Hide thumbs Also See for TH8320R1003 Vision Pro 8000:
Table of Contents

Advertisement

®
VISIONPRO
8000 WITH REDLINK™

WIRING

See Table 9 for Equipment Interface Module terminal descriptions and Table 10 for thermostat terminal descriptions.
Table 9. Equipment Interface Module Terminal Designation Descriptions.
Conventional System
Terminal
C
Common wire from 24 VAC transformer.
R*
Power wire from 24 VAC transformer.
RH*
Heating power
RC*
Cooling power
W
Heat Stage 1
W2
Heat Stage 2
W3
Heat Stage 3
Y
Compressor Stage 1
Y2
Compressor Stage 2
G
Fan Relay
A
Connect to Economizer Module or Lighting Panel
(TOD).
Universal relay for humidification,
U1 / U1
dehumidification, ventilation, or a stage of
U2 / U2
heating/cooling. U terminals are dry contacts that
U3 / U3
require power.
Universal input for a wired indoor sensor, outdoor
S1 / S1
sensor, discharge sensor, return sensor, dry
S2 / S2
contact device for alerts or dry contact device for
S3 / S3
remote setback.
S4 / S4
A
Connect to THM4000R1000 Wireless Adapter for
B
extended wireless range.
C
D
* Remove jumpers when separate transformers are used.
See "Wiring IAQ Equipment or a Heat/Cool Stage to the Universal Terminals" beginning on page 129.
See "Dry Contact Alerts" beginning on page 73 for wiring Dry Contact Devices to display alerts.
68-0312—01
Description
Terminal
C
Common wire from 24 VAC transformer.
R
Power wire from 24 VAC transformer.
RH
Heating power
RC
Cooling power
O/B
Changeover valve for heat pumps
AUX 1
Backup Heat Stage 1/Emergency Heat Stage 1
AUX 2
Backup Heat Stage 2/Emergency Heat Stage 2
Y
Compressor Stage 1
Y2
Compressor Stage 2
G
Fan Relay
L/A
Connect to Compressor Monitor, Zone Panel,
Economizer Module or Lighting Panel (TOD).
Universal relay for humidification,
U1 / U1
dehumidification, ventilation, or a stage of
U2 / U2
heating/cooling. U terminals are dry contacts that
U3 / U3
require power.
Universal input for a wired indoor sensor, outdoor
S1 / S1
sensor, discharge sensor, return sensor, dry
S2 / S2
contact device for alerts or dry contact device for
S3 / S3
remote setback.
S4 / S4
A
Connect to THM4000R1000 Wireless Adapter for
B
extended wireless range.
C
D
116
Heat Pump
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Th8321r1001 vision pro 8000Th8110r1008 vision pro 8000

Table of Contents