Advertisement

-
Remove the gas from the refrigerant circuit using recovery
equipment to avoid harming the atmosphere.
-
Electrically disconnect the compressor.
-
Unbraze or unscrew the suction and discharge lines,
taking care not to damage the rest of the components.
-
Remove the fastenings from the compressor.
-
Replace the compressor, ensuring that it contains
sufficient oil.
-
Braze or screw in the lines.
-
Connect the compressor according to the wiring diagram.
-
Evacuate the compressor.
-
Fill in the refrigerant charge indicated on the nameplate,
plus the required charge for the refrigerant connection
lines, if the system is a split system.
NOTE: This operation must be done by a qualified technician.

Description of unit protection devices

The unit includes the following unit protection devices:
-
Internal compressor protector to avoid overheating.
-
Short-cycle protection (included in the main electronic
board).
-
Outdoor fan motor thermomagnetic switch.
-
Indoor fan motor thermomagnetic switch.
-
High pressurestat - This protects the unit against
excessive condensing pressure. The high pressurestat has
factory-fixed non-adjustable settings. To check, see
section Initial checks.
-
Low pressurestat - This protects the unit against
excessive low pressure in the evaporator. The low
pressurestat has factory fixed non-adjustable settings. To
check, see section Initial checks.
CAUTION: When any of these cuts out, the unit stops and will
not re-start until the contacts have been reclosed after
rectification of the fault.
Table 5 - Pressure switch settings
Cut-out
High pressurestat
*2844 kPa
Low pressurestat
*265 kPa
* Factory-fitted
WARNING: Alteration of factory settings other than the design
set-point, without manufacturer's authorisation, may void the
warranty.

Operating limits

These units have been designed to operate within the following
limits:
Table 6 - Cooling operation
Zone
Air temperature
Dry bulb
Indoor
Maximum
35°C
Minimum
19°C
Outdoor
Maximum
46°C
Minimum
19°C*
* With the optional head pressure control, the unit can operate with temperatures below 19°C.
32
Cut-in
Reset
1863 kPa
Automatic
363 kPa
Automatic
Wet bulb
21°C
14°C
-
-
Table 7 - Heat pump operation
Zone
Air temperature
Dry bulb
Indoor
Maximum
27°C
Outdoor
Maximum
24°C
Minimum
-15°C

OPTIONS AND ACCESSORIES

Head pressure control kit
Electric heating
Compressor crankcase heater (standard on 50PZ) x
Hot water coil
Economizer
Outdoor air filter
User interface
Protection grille
Minimum opening potentiometer
Volt-free contacts
Optional communications
Return air sensor
Superior drive
38VZ/PZ for vertical discharge

Hot water heating coil

This option/accessory consists of the water heating coil, the air
flow equalising plate, the side access panel and fixing
components.
The heating coil performances are in accordance with Eurovent
conditions and are shown in tables 8 and 9.
Unit
015 025 030 031 040 045 055 065 075
Heating capacity
kW* 9.6
17.5 19.6 19.6 27.3 33.4 35.3 41
Water flow
l/s
0.46 0.84 0.94 0.94 1.31 1.60 1.69 1.96 2.09
Pressure drop
kPa 13
20
* Indoor air temperature 20°C and entering/leaving water temperature 50°C/45°C.
Unit
015 025 030 031 040 045 055 065 075
Heating capacity
kW* 15.2 27.9 30.4 30.4 43.4 51.5 54.6 63.9 68.5
Water flow
l/s
0.36 0.67 0.72 0.72 1.04 1.23 1.31 1.52 1.64
Pressure drop
kPa 9
13
* Indoor air temperature 20°C and entering/leaving water temperature 70°C/60°C.
Water connection
The entering and leaving water connections are all threaded
male gas connections with the diameters shown in Table 10.
Unit
015
025
030
Ø connection
1"
1"
1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/2" 1-1/2"
Wet bulb
-
18°C
-
Option
x
x
x
x
x
x
x
x
x
x
x
x
Table 8
14.5 14.5 13.5 21
23
Table 9
9
9
9
13
14.5 21
Table 10
031
040
045
055
Accessory
x
x
x
x
x
x
x
x
x
x
43.8
33.5 37.5
24
065
075

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50pz38pz40pz38vz

Table of Contents