LG LMN078HVT Installation & Maintenance page 25

Hide thumbs Also See for LMN078HVT:
Table of Contents

Advertisement

F
MULTI
F
MULTI
MAX
No Pipe Size Substitutions
Note:
Use only the pipe size recommended by this installation manual. Using a different size is prohibited and may result in system malfunction or failure.
Copper Expansion and Contraction
Under normal operating conditions, the vapor pipe temperature of a
Duct Free System can vary as much as 280°F. With this large vari-
ance in pipe temperature, the designer must consider pipe
expansion and contraction to avoid pipe and fitting fatigue failures.
Refrigerant pipe along with the insulation jacket form a cohesive unit that
expands and contracts together. During system operation, thermal heat
transfer occurs between the pipe and the surrounding insulation.
If the pipe is mounted in free air space, no natural restriction to
movement is present if mounting clamps are properly spaced and
installed. When the refrigerant pipe is mounted underground in a
utility duct stacked among other pipes, natural restriction to linear
movement is present. In extreme cases, the restrictive force of
surface friction between insulating jackets could become so great
that natural expansion ceases and the pipe is "fixed" in place. In this
situation, opposing force caused by change in refrigerant fluid/vapor
temperature can lead to pipe/fitting stress failure.
The refrigerant pipe support system must be engineered to allow
free expansion to occur. When a segment of pipe is mounted
between two fixed points, provisions must be provided to allow pipe
expansion to naturally occur. The most common method is the
inclusion of expansion Loop or U-bends. Each segment of pipe has
a natural fixed point where no movement occurs. This fixed point is
located at the center point of the segment assuming the entire pipe
is insulated in a similar fashion. The natural fixed point of the pipe
segment is typically where the expansion Loop or U-bend should be.
Linear pipe expansion can be calculated using the following formula:
LE = C x L x (T
– T
) x 12
r
a
LE
=
Anticipated linear tubing expansion (in.)
C
=
Constant (For copper = 9.2 x 10
L
=
Length of pipe (ft.)
T
=
Refrigerant pipe temperature (°F)
R
T
=
Ambient air temperature (°F)
a
12
=
Inches to feet conversion (12 in./ft.)
GENERAL INSTALLATION GUIDELINES
in./in.°F)
-6
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
1. In Table 16 find the row corresponding with the actual length of
the straight pipe segment.
2. Estimate the minimum and maximum temperature of the pipe.
In the column showing the minimum pipe temperature, look up the
anticipated expansion distance. Do the same for the maximum
pipe temperature.
3. Calculate the difference in the two expansion distance values.
The result will be the anticipated change in pipe length.
Example:
A system is installed and the design shows that there is a 100 foot
straight segment of tubing between an indoor unit and the outdoor
unit. In heating, this pipe transports hot gas vapor to the indoor units
at 120°F. In cooling, the same tube is a suction line returning refrig-
erant vapor to the outdoor unit at 40°F. Look up the copper tubing
expansion at each temperature and calculate the difference.
Vapor Line
Transporting Hot Vapor: 100 ft. pipe at 120 °F = 1.40 in.
Transporting Suction Vapor: 100 ft. pipe at 40 °F = 0.40 in.
Anticipated Change in Length: 1.40 in. – 0.40 in. = 1.00 in.
Liquid Line
The liquid temperature remains relatively the same temperature; only
the direction of flow will reverse. No significant change in length of
the liquid line, therefore, is anticipated.
When creating an expansion joint, the joint height should be a
minimum of two times the joint width. Although different types of
expansion arrangements are available, the data for correctly sizing
an Expansion Loop is provided in Table 1010. Use soft copper with
long radius bends on longer runs or long radius elbows for shorter
pipe segments. Using the anticipated linear expansion (LE) distance
calculated, look up the Expansion Loop or U-bend minimum design
dimensions. If other types of expansion joints are chosen, design per
ASTM B-88 Standards.
Refrigerant Piping
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmn158hvtLsn180hsv4Lsn090hsv4Lsn120hsv4Lmn248hvt

Table of Contents