Specifications - LG LMN078HVT Installation & Maintenance

Hide thumbs Also See for LMN078HVT:
Table of Contents

Advertisement

F
MULTI
F
MULTI
MAX
Model Name
Nominal Cooling Capacity
(Btu/h)
1
Nominal Heating Capacity
(Btu/h)
1
Operating Range
Cooling (°F WB)
Heating (°F DB)
Fan
Type
Motor Output (W) x Qty.
Motor/Drive
Airflow Rate CFM (H/M/L)
Unit Data
Refrigerant Type
2
Refrigerant Control
Power Supply V, Ø, Hz
3
Rated Amps (A)
Sound Pressure Level ±3 dB(A)
(H/M/L)
4
Dimensions (W x H x D, in.)
Net Unit Weight (lbs.)
Shipping Weight (lbs.)
Power Wiring / Communications
Cable (No. x AWG)
5
Heat Exchanger (Row x Column
x Fin / inch) x Number
Pipe Size
Liquid (in.)
Vapor (in.)
Connection Size
Liquid (in.)
Vapor (in.)
Drain O.D. / I.D. (in.)
Nominal capacity is rated 0 ft. above sea level with corresponding refrigerant piping
1
length in accordance with standard length of each outdoor unit and a 0 ft. level difference
between outdoor and indoor units. All capacities are net with a combination ratio between
95 – 105%.
Nominal cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb
(DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and
75ºF wet bulb (WB).
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb
(DB) and 60ºF wet bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and
43ºF wet bulb (WB).
Table 4: Multi F Multi Zone Standard Wall-Mounted Indoor Unit Specifications
LMN078HVT
LSN090HSV4
7,000
9,000
8,100
10,400
198 / 177 / 162
247 / 230 / 212
33 / 30 / 26
33 / 30 / 27
35-1/4 x 11-3/8
34-13/16 x 11-1/4
x 8-9/32
x 8-1/4
23
20
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
LSN120HSV4
LMN158HVT
12,000
13,800
57-77
59-81
Cross Flow
14.4 x 1
Brushless Digitally Controlled / Direct
335 / 318 / 300
371 / 318 / 247
R410A
Electronic Expansion Valve (EEV)
208-230, 1, 60
0.2
39 / 36 / 31
43 / 39 / 34
34-13/16 x 11-1/4
35-1/4 x 11-3/8
x 8-1/4
20
26
4 x 18
(2 x 16 x 23) x 1
1/4
3/8
1/4
3/8
27/32, 5/8
This unit comes with a dry helium charge.
2
Acceptable operating voltage: 187V-253V.
3
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745 and
4
are the same in both cooling and heating mode. These values can increase due to ambient
conditions during operation.
All power wiring / communications cable to be minimum 18 AWG, 4-conductor, stranded,
5
shielded, and must comply with applicable local and national codes.
GENERAL DATA

Specifications

LSN180HSV4
14,300
18,000
16,500
20,800
76.0 x 1
572 / 501 / 434
0.3
37 / 33 / 28
40-9/16 x 12-13/16
x 8-9/32
x 9-13/16
23
31
36
(3 x 18 x 22) x 1
1/2
3/8
5/8
LMN248HVT
24,000
27,000
720 / 600 / 466
42 / 39 / 36
40-9/16 x 12-13/16
x 9-13/16
37
1/4
1/2
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmn158hvtLsn180hsv4Lsn090hsv4Lsn120hsv4Lmn248hvt

Table of Contents