System Name
System Diagram
G. Timer operation
Enables control
of start and stop.
* For control by
external timer,
refer to Remote/
handheld com-
bined control op-
eration".
H.Interlock opera-
tion with periph-
Lossnay
eral equipment
ventilator
Enables control of
Mitsubishi Lossnay
ventilator by remote
controller.
Main
I.Rotation
• Weekly timer:
In addition to ON/OFF, up to eight temperature
patterns can be set for each day of the week.
* Only one timer can be selected; the auto off, simple
and weekly timers cannot be combined.
• Simple timer: Start and stop operations can each be
• Auto off timer: Operation is stopped when the preset
* Only one timer can be selected; the simple and auto
off timers cannot be combined.
• Connecting a Lossnay ventilator and an indoor unit
Indoor unit
enables control of interlock/solo ventilation opera-
tion and airflow.
(Only the microcomputer type Lossnay ventilator
Remote
can be used.)
Controller
When abnormality occurs while operating, it changes
Remote
into operating the back up unit, and operating is
Controller
continued.
Indoor
(Unit function Mode No. 20 setting No.3 , Indoor
Sub
unit
controller board SW-5-4 ON)
Outdoor
Main / Sub setting
unit
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
Each system operates alternately for 24 hours or 168
hours.
(Unit function Mode No. 20 setting No.1: 24
hours/No.2 : 168 hours, Indoor controller board SW 5-
4 ON)
Main / Sub setting
Main : Indoor controller board
SW5-3 : OFF
Sub : Indoor controller board
SW5-3 : ON
Features
performed once within 72 hours (can
be set in 1-hour increments).
time elapses following the start of
operation.
The time can be set from 30 minutes
to 4 hours in 30-minute increments.
63
Parts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
MA Remote controller
(PAR-21MAA)
This system can correspond only by
the pattern of two refrigerant group
by 1 : 1 (indoor and outdoor unit
combination) systems.