Emergency Operation Procedure; Self-Diagnosis; Wiring Diagram - Mitsubishi PLH-3AAK Technical & Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for PLH-3AAK:
Table of Contents

Advertisement

6

WIRING DIAGRAM

PLH-3AAK
PLH-4AAK
PLH-3AAKH PLH-4AAKH PLH-5AAKH
[LEGEND]
SYMBOL
NAME
P.B
INDOOR POWER BOARD
I.B
INDOOR CONTROLLER BOARD
FUSE
FUSE(T6.3AL250V)
ZNR
VARISTOR
BCR
FAN CONTROL ELEMENT
CN2L
CONNECTOR(LOSSNAY)
CN32
CONNECTOR(REMOTE SWITCH)
CN41
CONNECTOR(HA TERMINAL-A)
CN51
CONNECTOR(CENTRALLY CONTROL)
LED1
POWER SUPPLY(I.B)
LED2
POWER SUPPLY(R.B)
X1
RELAY(DRAIN PUMP)
X4
RELAY(FAN MOTOR)
SW1
SWITCH(MODEL SELECTION)WSee table 1
SW2
SWITCH(CAPACITY CORD)WSee table 2
SW5
SWITCH(SYSTEM SELECTION)WSee table 3
SW6
SWITCH(EMERGENCY OPERATION)
SWE
CONNECTOR(EMERGENCY OPERATION)
GRILLE
MV
MV
MV
MV
5
5
5
5
MF
1
2
3
6
7
4
1
2
3
1
2
3
DP
C
I.B
D.U.M
D.HEATER
FAN
1
3
5
1
3
1
CNC(RED)
(WHT)
CNP
(BLU)
X4
BCR
X4
X1
X1
HEATER
SWE
SW1
SW2
SW5
CN24
ON
(YLW)
OFF
DS
Refer to tables
1. 2 and 3.
NOTES:
1.Symbols used in wiring diagram above are,
2.Indoor and outdoor connecting wires are made with polarities, make wiring
matching terminal numbers (1, 2, 3).
3.Since the outdoor side electric wiring may change be sure to check the outdoor
unit electric wiring for servicing.

[Self-diagnosis]

1.For details on how to operate self-diagnosis with the wireless remote control, refer to the
technical manuals etc.
2.For the wired remote control:When you quickly press twice the CHECK switch on the
remote control, the unit begins self-diagnosis.
and Check Codes generated in the past appear on the display.
For Check Codes and symptoms refer to the table below.
Check Code
Abnormality of room temperature thermistor (TH1).
P1
Abnormality of pipe temperature thermistor/Liquid (TH2).
P2
Abnormality of drain sensor (DS).
P4
Malfunction of drain-up machine.
P5
Freezing / overheating protection is working.
P6
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.
P8
E0-E5
Abnormality of the signal transmission between remote controller and indoor unit.
Fb
Abnormality of indoor controller board.
No trouble generated in the past.
----
No corresponding unit.
FFFF
PLH-5AAK
SYMBOL
C
CAPACITOR(FAN MOTOR)
MF
FAN MOTOR
MV
VANE MOTOR
H2
DEW PREVENTION HEATER
DP
DRAIN-UP MACHINE
DS
DRAIN SENSOR
TB2
TERMINAL BLOCK (POWER SUPPLY)
TB4
TERMINAL BLOCK (INDOOR/
OUTDOOR CONNECTING LINE)
TB5, TB6
TERMINAL BLOCK(REMOTE
CONTROLLER TRANSMISSION LINE)
TH1
ROOM TEMP.THERMISTOR
(0:/15k",25:/5.4k" DETECT)
TH2
PIPE TEMP.THERMISTOR/LIQUID
(0:/15k",25:/5.4k" DETECT)
R.B
WIRED REMOTE CONTROLLER BOARD
CNSK
(RED)
CN2S
(WHT)
DC
2
5
H2
13.1V
1
8
9 5 10
5
VANE
3
1
3
1
3
POWER
1
2
1
1
2
2
3
CN6V
CND
POWER
POWER
OUTDOOR
(GRN)
(ORN)
CNDK
CN2D
CN30
(RED)
(WHT)
(BLK)
CN51
CN41
CN2L
ZNR
SW6
CN32
1 2
ON
LED2 LED1
OFF
D.SENSOR
INTAKE
LIQUID
REMOCON
CN31
CN20
CN21
CN22
WIRELESS
(WHT)
(RED)
(WHT)
(BLU)
CN90
1
2
3
1
2
1
2
1
2
(WHT)
TB5
2
TH1
1
TRANSMISSION WIRES
TH2
: Connector,
: Terminal (block).
Symptom
PLH-6AAK
PLH-6AAKH
NAME
P.B
3
2
1
TB2
RED
L
POWER SUPPLY
BLU
N
~(1PHASE)
GRN/YLW
220-240V 50Hz
220V 60Hz
TB4
YLW
1
ORN
2
TO OUTDOOR UNIT
BRN
3
W.B
BZ
9
LED2
LED1
CNB
RU
SW1
SW2
R.B
1
2
TB6
DC12V
PLH - AAKH
C
( w i th h ea ter )
Pos i ti on of 88 H .
( for C on tr ol bo x)
TB4

[Emergency operation procedure]

1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work
if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly
Emergency Operation.
WNote on the wireless remote control: when the remote control does not function, it is possible to
activate Emergency Operation by using the indoor unit emergency operation switch (SW1,SW2 of the
wireless signal receiver board).
However,if the indoor unit microcomputer has failed,it is nesessary to proceed with points 2 and
3 below as in the case of the wired remote controller.
2.When you activate emergency operation of the cooling or heating, you have to set the switch (SWE) and
switch (SW6) on the indoor controller.
SWE : ON
• Indoor fan is running at high speed. • Drain-up machine is working.
SW6-1 : ON
• Emergency operation of cooling mode.
SW6-1,2 : ON • Emergency operation of heating mode.
3.Before you activate emergency operation, check the following points:
(1) Emergency operation cannot be activated when:
• the outdoor unit malfunctions. • the indoor fan malfunctions.
• when it has detected the malfunction of drain-up machine during self-diagnosing.
(2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the
remote control or temperature control etc,dose not function.
(3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of
the heating is activated, because it will start to blow cold air.
(4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze).
(5) After emergency operation has been deactivated, set the switches etc.to their original positions.
(6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them
manually to the appropriate position.
31
SYMBOL
NAME
W.B
WIRELESS REMOTE CONTROLLER BOARD
RU
RECEIVING UNIT
BZ
BUZZER
LED1
LED(RUN INDICATOR)
LED2
LED(HOT ADJUST)
SW1
SWITCH(HEATING ON/OFF)
SW2
SWITCH(COOLING ON/OFF)
HEATER
FS1
THERMAL FUSE(72:, 16A)
FS2
THERMAL FUSE(104:, 16A)
H1
HEATER
26H
HEATER THERMAL SWITCH
88H
HEATER CONTACTOR
Table 1
Table 3
SW1
SW5
MODELS
MODELS
Manufacture/Service
Manufacture/Service
1 2 3 4 5
1 2 3 4 5 6 7 8
PLH-AAK
ON
PLH-AAK
OFF
1 2 3 4 5
1 2 3 4 5 6 7 8
PLH-AAKH
ON
PLH-AAKH
OFF
Table 2
SW2
MODELS
Manufacture/Service
MODELS
Manufacture/Service
1 2 3 4 5
1 2 3 4 5
PLH-3AAK
PLH-5AAK
ON
PLH-3AAKH
PLH-5AAKH
OFF
1 2 3 4 5
1 2 3 4 5
PLH-4AAK
PLH-6AAK
ON
PLH-4AAKH
PLH-6AAKH
OFF
[PLH-AAKH models only]
TB2
88H
FS1
L
RED
RED
RED
POWER SUPPLY
1
~(1PHASE)
N
BLU
WHT
2
220-240V 50Hz
GRN/YLW
220V 60Hz
HEATER CN24
(YLW)
1
2
I.B
88H
88H
Please set the voltage using the
remote controller.
For the setting method. please refer to
the indoor unit Installation Manual.
TB2
ON
OFF
ON
OFF
ON
OFF
ON
OFF
H1
FS2
26H
WHT
6
GRY
WHT
5