Electrical - Line Voltage - Carrier 50YFV Installation, Operation And Maintenance Instructions

Gt-pb series residential digital horizontal & vertical packaged geothermal heat pumps
Table of Contents

Advertisement

R e s i d e n t i a l D i g i t a l P a c k a g e d U n i t s G T- P B S e r i e s - 6 0 H z P u r o n
WARNING!
WARNING! To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
CAUTION! Use only copper conductors for fi eld installed
electrical wiring. Unit terminals are not designed to accept
other types of conductors.
Table 7a: GT-PB (50YF) Series Electrical Data with Magna
Internal Flow Controller
Compressor
HWG
Model
Pump
FLA
RLA
LRA
Qty
024
11.7
58.3
1
0.5
030
13.1
73.0
1
0.5
036
15.3
83.0
1
0.5
042
17.9
96.0
1
0.5
048
21.2
104.0
1
0.5
060
27.1
152.9
1
0.5
Rated Voltage of 208-230/60/1
HACR circuit breaker in USA only
Table 7b: GT-PB (50YF) Series Electrical Data with
Modulating Valve
Compressor
Model
RLA
LRA
Qty
024
11.7
58.3
1
030
13.1
73.0
1
036
15.3
83.0
1
042
17.9
96.0
1
048
21.2
104.0
1
060
27.1
152.9
1
Rated Voltage of 208-230/60/1
HACR circuit breaker in USA only
Int
Fan
Total
Min
Loop
Motor
Unit
Circuit
Pump
FLA
FLA
Amps
FLA
1.7
3.9
17.8
20.7
1.7
3.9
19.2
22.4
1.7
3.9
21.4
25.2
1.7
5.2
25.3
29.7
1.7
5.2
28.6
33.9
1.7
6.9
36.2
42.9
Min/Max Voltage of 197/254
All fuses Class RK-5
HWG
Fan
Total
Min
Pump
Motor
Unit
Circuit
FLA
FLA
FLA
Amps
0.5
3.9
16.1
19.0
0.5
3.9
17.5
20.7
0.5
3.9
19.7
23.5
0.5
5.2
23.6
28.0
0.5
5.2
26.9
32.2
0.5
6.9
34.5
41.2
Min/Max Voltage of 197/254
All fuses Class RK-5

Electrical - Line Voltage

All fi eld installed wiring, including electrical ground, must
comply with the National Electrical Code as well as all
applicable local codes. Refer to the unit electrical data for
fuse sizes. Consult wiring diagram for fi eld connections that
must be made by the installing (or electrical) contractor.
All fi nal electrical connections must be made with a length of
fl exible conduit to minimize vibration and sound transmission
to the building.
General Line Voltage Wiring
Be sure the available power is the same voltage and phase
shown on the unit serial plate. Line and low voltage wiring
must be done in accordance with local codes or the National
Electric Code, whichever is applicable.
Power Connection
Max
Line voltage connection is made by connecting the incoming
Fuse/
line voltage wires to the "L" side of the contactor as shown in
HACR
Figure 21. Consult Tables 7a through 7b for correct fuse size.
30
208 Volt Operation
35
All residential 208-230 Volt units are factory wired for 230
40
Volt operation. The transformer may be switched to the 208V
45
tap as illustrated on the wiring diagram by switching the red
50
(208V) and the orange (230V) wires at the contactor terminal.
70
Figure 24: GT-PB Single Phase Line Voltage
Field Wiring
Max
Fuse/
HACR
30
30
35
45
50
60
Unit Power Supply
(see electrical tables 7a - 7b for minimum
circuit amps and maxiumum breaker size)
R e v : 4 A p r i l , 1 4
Electrical - Line Voltage
®